Heating priority
It is possible to connect the water filtration pump to the heat pump, in order to start the filtration
pump if the water is not at desired temperature.
This connection must be done by connected P1 connection from the heat pump to the neutral
connection of the filtration pump and P2 to the phase connection of the filtration pup.
Maximum intensity used by the filtration pump wust be lower than 15A !
It is very important to connect 1 to neutral and 2 to phase. An inversion will destroy
heat pump and/or filtration pump.
Water flow detection
The heat pump only operates whenever there is water flow circulating inside. All models
are equipped with a water flow switch.
Utilization
Water connection
After having connected the heat pump to the pool water circuit system trough a suitable by-
pass and having made the electrical connections by a qualified engineer, please verify the
following points:
• Appliance is in a horizontal position and on a solid ground.
• Water circuit is primed (full of water): no air inside the tubes or the heat pump tank.
• Water circuit is well connected (no leaks and no chance of injury due to badly fitted
hydraulic couplings).
• Electrical circuit is well connected (all cables tightened correctly at terminals and
intermediate circuit breaker), insulated and earthed correctly.
• The installation requirements described previously are strictly adhered to.
• Ambient temperature is between : + 5 and + 35°C
By-pass diagram