3.5.2
DIP switch
The DIP switch on the control circuit board enables regulation and control of setpoints and limit values for
temperatures.
DIP switch (1) position
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
 Switch off the cooling unit for changes to the DIP switch. The new settings of the DIP switch take effect with
next commissioning.
The factory setting is as follows:
 The switch cabinet temperature setpoint is 35°C.
 The maximum switch cabinet temperature is 50°C.
Operating Manual DTS and DTI 6401 Standard Controller (SC) 086100013 © Pfannenberg GmbH
Figure 13 -– DIP switch
Temperatures in °C
Switch position 4 OFF = °C
3
Setpoint
OFF
25°C
OFF
30°C
OFF
35°C
OFF
35°C
ON
40°C
ON
40°C
ON
45°C
ON
45°C
Switch position 4 ON = °F
Max. limit value
Setpoint
45°C
77°F
45°C
86°F
45°C
95°F
50°C
95°F
50°C
104°F
55°C
104°F
55°C
113°F
60°C
113°F
Temperatures in °F
Max. limit value
113°F
113°F
113°F
122°F
122°F
131°F
131°F
140°F
Page 21 / 38