6. Communication Interfaces
5
USB Port
The USB port built into the UPS provides a RS-232 serial over USB connection. This allows a serial data stream for computers and
laptops that do not have the standard DB9-type serial port common with RS-232 connections. Once configured in Windows, this
port displays and operates as a standard COM port.
6
Output Dry Contacts
P1 P2 P3 P4 P5 P6
Pin 1 2 3 4 5 6 7 8 9 10 11 12
The SmartOnline SUT UPS provides six sets of programmable output dry contacts to deliver UPS events. There are eighteen
selectable events, six may be selected. The dry contacts are open by default. Please refer to the table below.
No.
Event
1
On-line Mode
2
Bypass Mode
Battery Mode
3
4
Low battery
5
Bypass input not OK
Battery test fail or battery
6
missing
UPS
(Figure 6-4: Output Dry Contacts: Pin Definition and Design)
Description
1. The UPS is in Normal Mode.
2. Default: Pins 1 and 2.
1. The UPS is in Bypass Mode.
2. Default: Pins 3 and 4.
1. When the main AC source fails, the UPS supplies battery power to the connected load.
2. Default: Pins 5 and 6.
1. When the UPS runs in battery mode, battery voltage is lower than setup limit, 220V DC.
2. Default: Pins 7 and 8.
1. The bypass voltage, frequency or phase sequence is abnormal.
2. Default: Pins 9 and 10.
1. In the process of battery test, battery voltage is out of setup limit.
2. Default: Pins 11 and 12.
26
DRY F_NO
COMM_F
DRY E_NO
COMM_E
DRY D_NO
COMM_D
DRY C_NO
COMM_C
DRY B_NO
COMM_B
DRY A_NO
COMM_A
+12VS
DRY 6
+12VS
DRY 5
+12VS
DRY 4
+12VS
DRY 3
+12VS
DRY 2
+12VS
DRY 1