Protection Of The Pump From Cavitation; Terms Of Use - Tecumseh INFINEE Serie Manuel D'installation Et De Maintenance

Groupes d'eau glacée
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Diagram:
Possibility of using a cable outlet with return (ref.
PLEXO ISO32 698 50 not supplied):

Protection of the pump from cavitation

For proper operation of the pump and to avoid cavitation, it is preferable to maintain suction pressure of
1 bar relative in operation. The NPSH of the pump is 0.99 m (absolute).

Terms of use

Our chillers are designed to operate in an ambient temperature range between -15°C and +46°c
The chillers are supplied with the optimum charge of R290 propane coolant. The charge is indicated on
the chiller data plate.
For all chiller terms of use, do not exceed the admissible maximum PS pressure (see data plate).
Version: 2020-01
Installation and maintenance manual
Remove the gland plate to assemble the cable
glands. The IP level of the box is IP44. In the
case of alteration or addition or otherwise, it is
necessary to take precautions and adequate
materials to retain this IP index.
Connect the three phases, neutral and ground to
the terminal block. Ensure the cable traction stop
by means of a collar in the base provided for this
purpose.
TECUMSEH EUROPE S&L
2 av. Blaise Pascal, 38090 Vaulx Milieu
Tel.: +33 (0)4 74 82 24 00 - www.tecumseh.com
INFINEE chillers
Earth
connection
dowel
ENGLISH
Traction
stop base
17