Operation
1. After running the guide/pull medium along the tray
length, place the medium into the feeder opening
by pinching either side detent pin set, which dis-
engages the idler rollers. Place the rope into the
opening between the drive roller and the idler
rollers, and re-engage the idler rollers to the detent
pins. Be sure that both pin sets are engaged before
drawing the cam lever into the loaded position.
Greenlee / A Textron Company
Squeeze
2. Plug in the device to any standard 115 VAC circuit
(refer to "Grounding Instructions"), and plug in the
pendant to the jack labeled pendant. Switch main
power to ON.
3. When the cable reaches the feeder, draw up the
idler rollers to the drive rollers by turning the cam
lever clockwise. When the cable is in contact on
both the idler rollers and the drive roller, draw the
cam lever across center where it will clamp on the
cable at the optimum load.
4. Activate the feeder by continuously pressing the
pendant rocker switch. Starting with the speed at
the lowest point, bring the speed up to match the
speed of the puller.
Note: If the cable pull has stopped and the feeder
has stalled, do not continue to activate the feeder.
Stalling the feeder may damage the motor.
5. When the cable has reached its destination, release
the pendant switch.
6. Relieve the clamp load in the idler assembly by
releasing the cam lever.
7. Remove the cable from the feeder by squeezing the
detent pin pair and releasing the idler roller so it is
free to rotate and set the cable down into the tray.
8. Repeat steps of operation.
7
4455 Boeing Dr. • Rockford, IL 61109-2988 USA • 815-397-7070
CTF-200