engelmann SensoStar A Instructions De Montage Et Manuel D'utilisation page 46

Compteur compact de chaleur

Publicité

Les langues disponibles

Les langues disponibles

LoRaWAN characteristics
Device class
LoRa version
Activation
Data rate
*OTAA
= Over-the-air activation
** ABP = Activation by personalization
1.4.2.2 LoRa module configuration
The module can be configurated by using the Device Monitors or the OTC App.
Parameter
Power mode
Configuration Lock
Synchronize meter time
Activation type
EcoMode
Transmit interval *[Min.]
Message format**
Pulse input selection
* The actual transmission interval depends on the type of telegram and the current data rate. The transmission
interval is adjusted accordingly in order to guarantee the set battery life (Eco Mode 10 or 6 years). You can find
more information in the „Manual LoRa Module".
** For pulse input option, the telegram type „Engelmann" must be selected.
1.4.2.3 Activation of the radio interface
The radio interface is deactivated by default and can be activated in one of the three following ways:
a)
NTC interface - via Elvaco OTC App; further information is available in the operating instructions of the Elvaco
OTC App:
https://www.elvaco.se/Image/GetDocument/en/269/elvaco-otc-app-manual-english.pdf
b)
Optical interface - via the Engelmann configuration software Device Monitor – from version 2.22; further
information is available in the operating instructions of the Device Monitor. The software can be ordered
separately.
c)
Via the heat meter menu;
Press and hold the button to switch to display loop "6" (= module loop; see Chapter
3 Display in the Module Loop (Optional)). Then switch to the second loop with a
short press of the button – 6-02 – „EnA oFF" (see image).
In order to start the edit mode, you must then press the key
press once more for 2-3 seconds. As an aid, an "editing pen" symbol appears in the
lower left corner of the LCD after 2 seconds. As soon as it can be seen, you must
Page 46 of 79
Article no.: 1080621031
Class A, Bi-directional
1.0.2 Rev B
OTAA* or ABP*
DR0-DR5 (250 bit/s-5470 bit/s)
Possible settings
Active
Inactive
Open
Locked
on
off
OTAA
ABP
off
6 years
10 years
5 ... 1440
Standard
Engelmann
Compact
JSON
Scheduled - daily redundant
Scheduled - extended
Combined heat/cooling
Choice between 0-3 pulse inputs
2022_02_02
Factory setting
Inactive
Open
off
OTAA
EcoMode 10 years
60
Standard
0
Subject to technical change! Errors excepted.