Stahl 9182 Serie Mode D'emploi page 20

Transmetteur de température
Masquer les pouces Voir aussi pour 9182 Serie:
Table des Matières

Publicité

Divers
FR
FR
FR
Type 9182/*0-5*-1*
FR
FR
FR
FR
FR
FR
FR
Hazardous area:
FR
Safe area:
FR
The Temperature Transmitter Type 9182 is an associated apparatus and provides intrinsically safe connections for one (or two) field
devices located in Class I, II, III, Division 1, Group A-G, hazardous locations according to NEC Article 504 as listed below.
FR
Temperature Transmitter Type 9182/a0-5b-1c
a = numeral 1 or 2 for number of channels
FR
b = numeral 0, 1, 3 or 9 for analog output
c = numeral 1 or 2 for number of contacts
FR
Entity parameters for wiring configurations are as follows:
FR
FR
Type 9182/*0-5*-1*
FR
Maximum supply current (at 18 V DC source, terminals 7+ and 9-):
9182/10-51-11
FR
110 mA
FR
Notes:
1. Intrinsically safe apparatus may be Simple Apparatus in accordance with Article 504 of the National Electrical Code, ANSI/NFPA 70
(for example: switches, thermocouples, LEDs, RTDs) a third-party certified or Entity device connected in accordance with the
FR
manufacturer´s installation instructions.
2. For Entity concept use the appropriate parameters to ensure the following:
FR
FR
3. Capacitance and inductance of the field wiring from the intrinsically safe equipment to the associated apparatus shall be calculated
and must be included in the system calculations as shown above. Cable capacitance (Cc) plus intrinsically safe equipment
FR
capacitance (Ci) must be less than the marked capacitance (Ca or Co) shown on any associated apparatus used. The same applies
for inductance (Lc, Li and La or Lo, respectively). Where the cable capacitance and inductance per foot are not known, the following
values shall be used: Cc=60pF/ft., Lc=0.2µH/ft.
FR
4. Electrical apparatus connected to an intrinsically safe system should not use or generate voltages > 250 V (U
5. Instrinsically safe circuits must be installed, wired and separated in accordance with Article 504.20 of the National Electrical Code
(ANSI/NFPA 70)
6. Where multiple circuits extend from the same piece of associated apparatus, they must be installed in separate cables or in one
cable having suitable insulation. Refer to Article 504 of the National Electrical Code and Instrument Society of America
Recommended Practice ISA RP12.6 for installing intrinsically safe equipment.
7. Associated Apparatus must be installed in an enclosure suitable for the application in accordance with the National Electrical Code,
ANSI/NFPA 70.
8. Use an UL or NRTL listed Dust-ignition proof enclosure appropriate for environmental protection in
Class II, Division 1, Groups E,F and G; and Class III, hazardous (classified) locations.
9. The isolators have not been evaluated for use in electrical combination with other associated apparatus.
10. These modules are to be mounted on DIN rail, DIN rail with pac-Bus (type 9194) or pac-Carrier (type 9195).
The field wiring in any case is connected to the IS pac device terminals.
11. Ambient temperature:
WARNING:
20
Transmetteur de température
Série 9182
Class I, II, III; Div. 1; Group A-G; Hazardous Locations
Non-hazardous Locations
V
I
P
OC
SC
O
6.5 V
19.7 mA
32 mW
9182/10-51-12
9182/10-50-12
120 mA
90 mA
d V
t C
V
or V
C
t
OC
max
a
d I
t L
I
or I
L
t
SC
max
a
-20 °C ... +70 °C (any mounting position)
To prevent ignition of flammable or combustible atmospheres disconnect power before servicing
2007
18.04.
Einsiedle
18.04.
(only 9182/2)
L
L
o
o
CL.I, Div.1, A,B
CL.I, Div.1, C-G
90 mH
330 mH
9182/20-51-11
9182/20-50-12
9182/10-59-11
130 mA
100 mA
+ C
i
Cable
+ L
i
Cable
Certification drawing
r
Temperature Transmitter
Kaiser
Type 9182
91 826 01 31 3
C
C
o
o
CL.I, Div.1, A,B
CL.I, Div.1, C-G
25 µF
570 µF
9182/10-59-12
90 mA
90 mA
).
max
169038 / 9182604310
2013-08-14·BA00·III·fr·10
none
1 of 1