Operating side
Operating side
Heat recovery
Heat recovery
Device division
Device division
Filter class
Filter class
Multileaf dampers
Multileaf dampers
Surface (interior / exterior)
Surface (interior / exterior)
Dimensions(mm)
Dimensions(mm)
Duct connection(mm)
Duct connection(mm)
Weight(kg)
Weight(kg)
Total amount
Total amount
Information requirements for NRVUs as referred to in Article 4(2):
Typology: NRVU, BVU
Type of installed drive: see drive information
Type of HRS: other
Filter warning indication
Decomposition drawing:
For safety notes regarding disassembly and disposal, please refer to the transport and installation manual for 'Air handling
units, X-CUBE Compact including X-CUBE Compact accessories'. The manual is shipped with the air handling unit, but can
also be downloaded from http://www.troxtechnik.com.
HRS thermal efficiency:
Nominal NRVU flow rate:
Effective electric power input:
SFP int:
Face velocity at design flow:
Nominal external pressure:
Internal pressure drop of ventilation components:
Static efficiency at operating point:
Static efficiency according to EU 327:
Internal leakage:
External leakage:
Energy performance of the filters:
Sound power level:
Eco design requirements for RVUs 2016:
Eco design requirements for RVUs 2018:
Unit details:
Supply and extract air unit, compact construction, with highly efficient heat recovery. The high-quality casing is a frame construction with
fitted double skin panels, powder-coated on both sides, for demanding hygiene requirements. Unit is ready to operate due to integral, bus-
based X-CUBE control system; prepared for BACnet and Modbus; other bus systems are possible. (Duct connection and electrical
connections are to be made by others.) Quick-release filter clamping device and high-quality F7 minipleat filter inserts for both supply air and
extract air. Fresh air and exhaust air multileaf dampers with aerodynamically profiled aluminium blades, low leakage to EN 1751, class 2; all
four duct connecting spigots prevent the transmission of structure-borne noise. Centrifugal fans with backward curved blades (plug fans) and
EC motors are infinitely variable and ensure optimum efficiency and the lowest sound pressure level even under partial loads; they comply
with the future IE4 efficiency class. All units are tested for CE conformity and carry the CE mark. Galvanised sheet steel, degreased, with
thick film iron phosphate. Powder-coated (approx. RAL 9016).
Version: 2.3.18 (04.05.2018)
Eurovent calculation based on X-CUBE
Configurator version 2.5
Easy Product Finder
X-CUBE-C-R-R/4200/3P/F7
Total
80,3
2,40
882
3,9
L1(M) / L2(R)
46
complied
complied
right
right
Heat wheel
Heat wheel
threefold
threefold
ePM1-60% (F7)
ePM1-60% (F7)
2 dampers inside (class 2, EN 1751)
2 dampers inside (class 2, EN 1751)
Powder-coated
Powder-coated
1738 x 1156 x 1518 (length x depth x height)
1738 x 1156 x 1518 (length x depth x height)
1062 x 557 (width x height)
1062 x 557 (width x height)
580
580
1
1
Supply/Extract air
4200 / 4200
1,20 / 1,20
441 / 441
1,7 / 1,7
250 / 250
239 / 239
54,3 / 54,3
66,1 / 66,1
Class B / Class B
Date: 13.06.2018 / DE
ErP-Datenblätter 2018
R/4200
%
m³/h
kW
W/(m3/s)
m/s
Pa
Pa
%
%
%
dB(A)