Lutron LOS-C Serie Instructions D'installation page 4

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Wiring Diagrams (continued)
1 to 3 Sensors with Power Pack
Line/Hot
120/277/347 V~ 60 Hz;
230 V~ 50/60 Hz
Neutral
Note: Maximum 3 occupant sensors.
Switching Multiple Loads with Auxiliary Power Packs
Line/Hot
120/277/347 V~ 60 Hz;
230 V~ 50/60 Hz
Neutral
Load
Note: Maximum of 3 devices total (occupant sensors and auxiliary power packs) can be connected to
a power pack.
*Note: Use gray wire for -R model.
Troubleshooting
Problem
Lights Stay On
Lights on too long
Hallway traffi c turns
lights on
Sensor not responding
World Headquarters
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036
TEL +1-610-282-3800
FAX +1-610-282-1243
Internet: www.lutron.com
E-mail: product@lutron.com
1
2
3
Auxiliary
Red
Power
Red
Pack
Possible Cause
Constant noise (e.g. air
vents, air handlers,
windows, fans, etc.)
Timer setting too high
Infrared sensor
"sees" into hallway
Unit is locked up
LIMITED WARRANTY
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after
purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd.,
Coopersburg, PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year
from purchase. This warranty does not cover the cost of installation, removal or reinstallation, or damage resulting
from misuse, abuse, or improper or incorrect repair, or damage from improper wiring or installation. This warranty
does not cover incidental or consequential damages. Lutron's liability on any claim for damages arising out of or in
connection with the manufacture, sale, installation, delivery, or use of the unit shall never exceed the purchase price
of the unit.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some
states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you.
)
Lutron and
are registered trademarks of Lutron Electronics Co., Inc. © 2013.
Power Pack
Red (+20-24 V
1
Blue * (signal)
2
Black (common)
3
1
2
Power Pack
3
Test
Reduce both green and
red knob by 15% or
temporarily remove noise
source
Check sensor settings
Put sensor in timer test
mode; walk along hallway
--
Black
Neutral
Red
Red
)
Black
Neutral
Red
Red
Action
Move sensor or temporarily
reduce sensitivity
Typical setting is 8 minutes
Move sensor
Cycle power to sensor
Load
Load
®