Display Brightness - Camille Bauer Digem f 96x48CK Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Delay Time
If the relays are not to respond immediately in the event of an alarm message, an integration time
constant can be selected. Selection is made as with switching hysteresis with the last digit in cod2.
Set the last digit of cod2 to xx2. Press the P key. dEL and a number blink alternately in the display.
This number represents delay time in seconds. Selection can be made within a range of 0 to 127s.
Select the desired time with the keys ⇑ and ⇓. Press the P key. cod3 and a number blink alternately
in the display.
Delay Time and Alarm Storage
If the measuring instrument requires a delay time, and must also store alarm messages, the last
digit of cod 2 must be set to xx5. The above procedure is followed as described for delay time.
Alarm Storage
If the storage of alarm messages is required without switching hysteresis or delay time, the last digit
of cod2 must be set to xx3.
5.8

Display Brightness

Display brightness can be adjusted with the "bri" parameter. The adjustment range runs from 0 to 7.
Brightness is set to 5 at the factory.
5.9
Temperature Display in ˚C and ˚F
The measuring instrument displays temperatures in either ˚C or in ˚F, as is indicated on the serial
plate. For display in ˚C, offset and scaling factor have the following values: offset = – 178, SCAL =
0.5556. For display in ˚F, offset and scaling factor have the following values: offset = 0, SCAL =
1.0000. Offset and scaling factor must be changed correspondingly, if display is changed from ˚C to
˚F, or vice versa.
6
Serial Interface for DIGEM f 96 x 48 CK (Option)
The instrument can be equipped with either an RS 232 or RS 485 interface (observe particulars on
serial plate). Transmission is accomplished with a transmission protocol in accordance with DIN
Draft no.19244.
DIGEM
20
GOSSEN-METRAWATT

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Digem f 96x48ek

Table des Matières