DDT40 TRIPPERS
In Refrigeration Mode
Arrow on timer points to current time.
"Green"
LED ON
"1 & F" Make
"1 & 3" Break
3
F
In Defrost Mode
Arrow on timer points to current time.
"Red"
LED ON
"1 & F" Break
"1 & 3" Make
3
F
Note: It is necessary to apply power across terminals 1&N in order to perform electrical test.
Note: Although wiring is equivalent, the DDT40 will not fit inside of a Paragon Enclosure. This enclosure will need to be
changed out with the provided Grasslin™ Enclosure.
Paragon
Precision
8045
6045
®
8041
6041
®
8047
6047
®
TIME INITIATED, REMOTE TEMPERATURE OR PRESSURE TERMINATED
8145
6415
®
8141
6141
®
8143
---
®
(Separate Presure Switch Required (see instructions))
8245
®
---
8247
®
---
Cross Ref.
DDT40 replaces over 40 models
DDT40 Adaptive Defrost Control
MODE A
Trippers are "IN"
Indicates
Refrigeration
CONTROL
TERMINATE
POWER
INPUT
"2 & 4" Make
1
2
4
N
X
L1
L2/N
Trippers are
"OUT"
Indicates
Defrost
CONTROL
TERMINATE
POWER
INPUT
"2 & 4" Break
1
2
4
N
X
L1
L2/N
Mode
Grässlin
™
Selection
TIME INITIATED, TIME TERMINATED
DDT40
DDT40
DDT40
DDT40
DDT40
DDT40
TIME INITIATED, PRESSURE TERMINATED
DDT40
DDT40
TABLE 1 Defrost Control Replacement Selector
Both LED's
OFF
"1 & F" Make
"1 & 3" Break
Both LED's
ON
"1 & F" Break
"1 & 3" Make
Terminal Ident.
Wiring
Label
Diagram
A
8045
A
8041
B
8047
A
None
A
8141
B
8143
A
8245
B
8247
6
DDT40 TRIPPERS
MODE B
In Refrigeration Mode
Arrow on timer points to current time.
CONTROL
POWER
F
3
1
2
4
L1
L2/N
In Defrost Mode
Arrow on timer points to current time.
CONTROL
POWER
3
1
2
4
F
L1
L2/N
Terminal Layout
F 3 1-N 2 4 X
5
N 1
3 2 4
2
N 1 3 4 2 2
4
F 3 1 2 4 N X
1, 6
N 1 3 2 4 X
7
1 N 3 4 2 X
8, 9
F 3 1-N 2 4 Xp p
10
N 1 3 2 4 Xp p
3
Trippers are "IN"
Indicates
Refrigeration
TERMINATE
INPUT
"2 & 4" Break
N
X
Trippers are
"OUT"
Indicates
Defrost
TERMINATE
INPUT
"2 & 4" Make
N
X
X