Ground Fault Circuit Interrupter Protection

These generators are equipped with a GFCI (Ground Fault Circuit
Interrupters) 120V duplex receptacles for protection against the hazards
of electrical shock from defective attachments such as, tools, cords,
and cables.
The GFCI may not function unless the generator is properly
grounded. Follow the correct procedure specified in the section
labeled GROUNDING INSTRUCTIONS.
A GFCI is a device that interrupts electricity from either the utility or
generator by means of a special type of circuit breaker that determines if
a current flow to the ground occurs.
A GFCI can be used only with generators that have the neutral wire
internally bonded to the frame, and the frame properly grounded to the
earth. A GFCI will not work on generators that do not have the neutral
wire bonded to the frame, or on generators which have not been properly
grounded. All New Holland Construction generators have internally
bonded ground wires.
THERE IS A PERMANENT CONDUCTOR BETWEEN THE GENERATOR (STATOR
WINDING) AND THE FRAME.