Operation
14
The AUDIBLE ALARM selection screen will appear.
 


To Advance to
To Change This
the Next Screen:
Setting:
Press SCROLL (
)
Press "SELECT" ( ^ )
v
15
The ALARM HISTORY selection screen will appear.
 


To Advance to
To Change This
the Next Screen:
Setting:
Press SCROLL (
)
Press "SELECT" ( ^ )
v
16
The INFORMATION screen will appear.



To Advance to
To Change This
the Next Screen:
Setting:
Press SCROLL (
)
Press "SELECT" ( ^ )
v
17
The ORIGINAL UPS SET-UP EXIT/ENTER screen will appear.
 


13-07-015-9332C3.indb 22
The AUDIBLE ALARM screen gives the user the ability to permanently enable or disable the
UPS's audible alarm in case of an alarm event. The factory configuration of ENABLE is ideal
for most applications. Certain applications may require the alarm to be disabled, in which
case the option of DISABLE can be selected.
ENABLE*
SCROLL
SELECT
ALARM HISTORY displays up to 5 alarm events. Possible alarms include CHARGER FAULT,
FAN FAULT, OVER TEMP , +/-DC BUS HIGH/LOW, BUS OVP , INVERTER FAULT, BATTERY FAULT,
DC-DC FAULT, OVERLOAD, O/P SHORT, NO BATTERY, SITE WIRE FAULT, BYPASS VOLT BAD,
BYPASS FREQ BAD, INPUT OVERCURRENT, and BATTERY LOW.
1: OVERLOAD
SCROLL
SELECT
INFORMATION refers to a series of 3 information screens that are viewable via the LCD
interface: Firmware version, UPS serial number and SNMP IP address. These values are for
viewing only and cannot be modified via the LCD interface
FW VER:FW#####
SCROLL
SELECT
Press EXIT (
) to exit the UPS SET-UP section.
v
Press "ENTER" ( ^ ) to re-enter UPS SET-UP screens.
22
Press SELECT ( ^ ) to SET this value.
Press SCROLL (
) to advance to the next option.
v
Available values are: ENABLE, DISABLE
Scroll through available values and press
SELECT ( ^ ) to SET.
Factory Default: ENABLE
Press "SELECT" ( ^ ) to SET this value.
Press "SCROLL" (
) to advance to the next option.
v
Available values are: ALARM HISTORY 1-5 &
ERASE
Scroll through available values and press
SELECT ( ^ ) to SET
Press "SELECT" ( ^ ) to EXIT this section.
Press "SCROLL" (
) to advance to the next
v
information screen.
Available Information: FIRMWARE VERSION,
UPS SERIAL #, SNMP IP ADDRESS
Scroll through available values and press
SELECT ( ^ ) to EXIT.