Operation
To Advance to
the Next Screen:
Press SCROLL (
)
v
13
The FACTORY DEFAULT selection screen will appear.
 

To Advance to
the Next Screen:
Press SCROLL (
)
v
Continued on page 22.
13-07-015-9332C3.indb 21
To Change This
Setting:
SCROLL
Press "SELECT" ( ^ )
UPS MODEL
SU3000RTXLCD2U
Scroll through available values and press SELECT ( ^ ) to SET.
Factory default = NO BP
If you're planning on using your UPS with the additional supported battery pack option
listed above as battery pack option 3, EXTERNAL BATTERY CONFIGURATION TOOL software
is required. After the EXTERNAL BATTERY CONFIGURATION TOOL software is used, the UPS
will display the resulting configuration as "BP TOOL" on the LCD screen. BP TOOL is present
as an LCD viewable option, but is itself not selectable (if BP TOOL selection is attempted,
the screen will report "READ ONLY. SELECT BY BP TOOL" to confirm the selection has not
been accepted). EXTERNAL BATTERY CONFIGURATION TOOL software is a Windows only
application and requires a serial cable connection to the UPS in order to run.
Visit http://www.tripplite.com/bpconfig to download the software.
Battery Pack Models That Require Use of EXTERNAL BATTERY CONFIGURATION TOOL
Software:
UPS MODEL
SU3000RTXLCD2U
FACTORY DEFAULT gives users a quick and easy way to return the UPS to its original factory
configuration. When selecting YES to FACTORY DEFAULT in the LCD Set-Up screens, the
UPS will immediately revert to the original shipping configuration and set of presets.

Running a FACTORY DEFAULT will restore these factory settings:
OUTPUT VOLTAGE = 120
OUTPUT FREQUENCY = 60Hz
BYPASS RANGE = WIDE
OVERLOAD ALARM = 105%
SHUTDOWN AFTER = DISABLE
BATTERY SAVE = DISABLE
STANDBY MODE = NO OUTPUT
FREQ CONVERTER = DISABLE
To Change This
Setting:
Press "SELECT" ( ^ )
SCROLL
Note: The UPS must be
in Standby Mode to
change this setting.
NO BP*
Press "SELECT" ( ^ ) to SET this value.
Press "SCROLL" (
SELECT
Available values are:
Configure via LCD
Factory
Battery pack
Battery pack
Default
option 1
option 2
NO BP
BP72V15-2U BP72V28RT-3U
BP72V28RT3U (for more than 1)
Press "SELECT" ( ^ ) to SET this value.
NO
Press "SCROLL" (
Available values are: NO, YES
SELECT
Scroll through available values and press SELECT
( ^ ) to SET.
Factory default = None
21
) to advance to the next option.
v
Configuration via EXTERNAL BATTERY
CONFIGURATION TOOL software
Battery pack option 3
(BP TOOL on LCD display)
BP72V28RT3U (for more than 1)
BATTERY PACK MODEL
ECONOMY MODE = DISABLE
COLD START = ENABLE
BATTERY TEST = MONTHLY
EXTERNAL BATT = NO BP
FACTORY DEFAULT = YES
AUDIBLE ALARM = ENABLE
ALARM HISTORY = ALL MESSAGES CLEARED
INFORMATION = NO CHANGE
) to advance to the next option.