6 Wiring Diagram / Schéma de câblage
Method 1, using two different circuits / Méthode 1, en utilisant deux circuits différents
E LE CTR ICAL PANE L
LIVE VAC BAR
NE UTR AL BAR
GR OUND BAR
LIGHTING S WITCH
CONTR OL S WITCH
ON
ON
THE R MOMAGNE TIC
THE R MOMAGNE TIC
CIR CUIT
BR E AKE R
G
N
L1
G
Method 2, using same circuit / Méthode 2, en utilisant le même circuit
E LE CTR ICAL PANE L
LIVE VAC BAR
NE UTR AL BAR
GR OUND BAR
CONTR OL S WITCH
ON
THE R MOMAGNE TIC
G
MINI INVE R TE R
X1
X2
VIN NE UT
GND
GND
VIN NE UT
CONTR OL
UTILITY
C ONTR OL S WITC H is intended for
CIR CUIT
circuit protection only, it must never
BR E AKE R
be turn off.
LIGHTING S WITC H is intended for
N
L1
circuit protection, and can be turn off
in case of customer wants to have
luminaires normally off.
MINI INVE R TE R
X8
X9
B3
VIN NE UT
GND
GND
VIN NE UT
CONTR OL
UTILITY
C ONTR OL S WITC H is intended for
circuit protection only, it must never
CIR CUIT
be turn off.
BR E AKE R
N
L1
X3
X4
X5
X6
X7
NC
COM
VOUT
NE UT
GND
DIMMING
CONTR OL
LOAD
OVE R R IDE
0 - 10V
S WIT C H
DIMME R
OPT IONAL
X10
X11
X12
X13
X14
NC
COM
VOUT
NE UT
GND
DIMMING
CONTR OL
LOAD
OVE R R IDE
0 - 10V
S WIT C H
DIMME R
OPT IONAL
5
To troubleshooting check these LE D indicators on this board.
When this LE D is flashing it indicates the microcontroller is running
properly.
This LE D will be flashing during the first 30 sec if the power is more
than 1440W and after that the inverter will turn off.
This LE D will be on if the battery fuse is burnt.
This LE D will be on if the inverter stopped because the battery
voltage reached the LVD (Low Voltage Disconnect).
LUMINAIR E S
To troubleshooting check these LE D indicators on this board.
When this LE D is flashing it indicates the microcontroller is running
properly.
This LE D will be flashing during the first 30 sec if the power is more
than 1440W and after that the inverter will turn off.
This LE D will be on if the battery fuse is burnt.
This LE D will be on if the inverter stopped because the battery
voltage reached the LVD (Low Voltage Disconnect).
LUMINAIR E S
MINI-INVERTER SERIES
IIS-MVP-MIV-GEN2_R02