Parameter Code
Internal parameter code is showing below:
Sort
Code
F11
F12
F13
Temperature
F14
F18
F19
Compressor
F21
Parameter
Name
Setting
F14 – F13
temperature
Temperature
difference
Max setting
-45 - +145
temperature
Min setting
-45 - +145
temperature
Evaporator
sensor
adjustment
Temp sensor
adjustment
Compressor
delay time
Factory
Range
setting
40
0.1 – 20
1.0
40
10
-20 – +20
0.0
-20 – +20
0.0
0 -- 10
3
Unit
Remark
The setting range is limited
℃
by F13 and F14
Control the temperature
difference, please refer to
℃
the temperature controlling
Notice: the controller will
follow the rule of
℃
F14<F11<F13 forcibly, if
you find out that one
parameter can not be
adjusted, it is because the
parameter is limited by
℃
other parameters, you must
first adjust other
parameters
Adjust the evaporator
sensor bias
℃
Adjust the temperature
sensor bias
℃
min
19