General Characteristics; Technical Data; Operating Voltage - SFA ZPS 1.3 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
this, various sensors for level measurement can be used: floating switches, dynamic pressure,
air bubble level measurement systems, external 4 - 20mA- sensors. The respective sensors to be
employed can be selected via the control program. Then pump are directly activated by the motor
contactors. Furthermore, the following devices for the error messages will be available: acoustic
signaler, 4 relay alarm contacts potential-free (programmable for: high-water, combined fault,
pump on, pump malfunction, unit working to specification), safety circuits in the form of a turn-on-
and a turn-off-delay, motor current monitoring systems, motor temperature monitoring systems and
flood control sensors guarantee a safe operation of the pump station.
The control system is operated via 6 short travel key switches, the program settings are displayed
on an LCD display. All settings are saved so that they are available when the control system is
restarted. The display language can be changed.
Besides the actual operational parameters, the control system also saves the controlling process
and the pump malfunctions in a record which can be displayed on the LCD display.

2.2 General characteristics

• Clear LCD display
• Hand- Stop- Auto- Function
• 1 acknowledgement button, 2 parameter
select buttons
• Menu which can be switched through
• Internal acoustic alarm
• Programmable operation and collective fault
signal potential-free
• Floating flood control potential-free
• Omnibus fault message potential-free
• Setting via short travel key switches
• Operating hours counter
• Maintenance interval counter
• Pump start counter

2.3 Technical data

Operating voltage

Voltage of control system
Power consumption
Pressure range
Turn-on-delay
Follow-up time
Runtime monitoring
Motor current limitation
Fault protocol memory
Maintenance interval counter
Operating temperature range
Dimensions
Max. pre-fuse
Potential-free alarm contact
Degree of protection
Housing
• Recording of fault protocol
• Electronic monitoring of the motor current
• Programmable turn-on-delay
• Programmable pump follow-up
• Programmable pump changeover interval
• Switchable service- and ATEX- mode
• Internal pressure sensor
• Level indication in cm
• 2 digital inputs for the thermostatic switch
• 3 digital inputs for the floating switch or reed
sensor
• 1 analogue input for transmitter 4-20mA
• 1 analogue pressure input 0-100(500) mBar
230V or 400V/AC/50-60 Hz
230V/AC/50-60 Hz
env. 6VA
0-1mWs
0-180 sec
0-180 sec
0-300 sec
0.5- 14A
32 memory positions
0 – 365 days, adjustable
-20 - +60°C
180x180x90 mm
20A
3 A max.
IP 65
Polycarbonate
5

Publicité

Table des Matières
loading

Table des Matières