Télécharger Imprimer la page

Technical Data - CEAG SPG 1N Série Instructions D'utilisation

Publicité

1. Safety Instructions
For skilled electricians and instructed
personnel in accordance with national
regulation, including the relevant standard and,
where applicable, in acc.with IEC 60079-17 on
electrical apparatus for explosive atmospheres.
¡The luminaires must not be operated in
Zones 0 and 20!
¡The tecnical data indicated on the luminaires
are to be observed!
¡Changes of the design and modifications to
the luminaires are not permitted!
¡The luminaires shall be operated as intended
and only in undamaged and perfect conditions!
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
¡Only genuine
spare parts may be used for replacement!
¡Repairs that affect the explosion protection, may
only be carried out by
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
"electrician" and will subsequenctly have to be
cheked by an "expert"!
Do not keep these operating instructions inside
the luminaire during opertion.
The national safety rules and regulations
for prevention of accidents and the
following safety instructions which are
marked with an (
) in theses operting
instructions, will hav to be observed.
2. Conformity with standards
This explosion protected luminaires meets the
requeriments of IEC/EN 60079-1,
IEC/EN 61241-1 and EN60598.
It also complies with the EC Directives for
"Apparatus and protective systems for use in
explosive atmospheres" (94/9/EC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
EN29001 (ISO9001).
The luminaire are suitables for use in explosive
atmospheres, Zone 1 and 2 acc. to acc. to
IEC60079-10 and Zones 21 and 22 acc.
IEC 61241-10.

3. Technical data

Application
II2GD
Class I:
Exd IIC T
Class II:
Ex tD A21 IP66 T
Certificates:
LOM 02 ATEX2018X
IECEx-BKI 07.0032X
Others, contact us
Serie of types:
See Table 1
Lamps to be use
4)
:
Lamps with lampholder
E27 acc. EN60061-1
Approval of the production
ATEX de Quality assurance:LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 66
Insulation class
acc. EN60598:
I
Temperature of use:
-50
o
C to + 55
≤ 250V
Rated voltage
Material of enclosure:
Metal aloy aluminium
without Cu,
painted polyester grey.
Material of glas
Borosilicate
Storage temperature
in original Packing
-40
o
C a + 60
Terminals capacity:
See wiring diagram
Entries of cables
Direct entry:
1 x ¾" ISO 7/1,
with PSL 11
for non armoured
cable Ø 10 - 14mm
Dimensions:
See figure 3.
Notes:
2) Special conditions for safe use of luminaires with direct entry.
The cable of the main connection will be adecuated for a temperature in confinuos service,follow indicated.:
Lamps 100W for Tamb –20
o
C / + 40
Lamps 60W and 70W for Tamb –20
3) See table 2, thermal class acc. the lamp used.
4) Non included.
4. Installation
¡The respective national regulations as well
as the general rules of engineering which
apply to the installation and operation of
explosion protected apparatus will have to
be observed!
¡Transport and storage of the luminaire is
permitted in original packaging only!
Opening and closing the luminaires
¡The opening of luminaire always shall be
without voltage!
¡The luminaire is well closed when the
glass-collar is completly threaded on the
luminaire enclosure!
Dimensions for mounting:
Accesories for mounting:
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
See
Cable entries
Included
or a qualified
Main conection:
Lamps mounting
¡Only must be mounting apropiated lamps for
the supplied luminaire. See indications in the
general label of the luminaire!
5.
Taking into operation
¡Prior to operation check the luminaire for
its proper funtioning and installation in
compliance with these operting instructions
and others applicable regulations!
Only carry out insulation measurements between PE
and external conductor L1 (L1, L2, L3) as well as
between PE and N.
-
measurement voltage: max. 1kV AC/DC
-
min. insulation: 2 MΩ
Then the luminaire have to be tightly closed.
6.
Maintenance
¡Observe the national rules applicable to
maintenance, servicing, inspection and
repairing of apparatus for explosive
atmospheres, as well as the general rules of
3)
engineering!
3)
¡For dust explosive application, pay special
2)
attention d'ont have present dust layers
2)
abore 5mm on side of the apparatus!
o
C
o
C
o
C, Tw cable > 105
o
C ; para Tamb –20
o
C / + 40
o
C, Tw cable > 100
o
C ; para Tamb –20
See figue 3
catalogue
See wiring diagram.
o
C / + 55
o
C, Tw cable > 120
o
C
o
C / + 55
o
C, Tw cable > 115
Servicing
The responsable of the safe use of these
apparatus is the property.
When servicing, in particular those components that
affect the explosion protection , will have to cheked,
e.g.:
Housing and glass for any cracks or damage.
The flameproof joint have to be clean,
undameged, without corrosion and perfect
greassed.
Gaskets for their perfect conditions.
Cable entries whitout corrosion.
Terminlas for their firm fit.
Lamp replacement in acc. with the manufacturer
instructions.
Type of lamps used in acc. with the luminaire
specifications.
¡The flameproof of these apparatus have to
be greassed permanentlly in order to ensure
it protection in front of the corrosion, water
ingrees and seize-up problems. Cleaning
rest of greasse and corrosion no using
sharp metallic devices who can damage the
surface of the joint, and greasing they using
apropiate greasse therminally and
chemically stable, like e.g.:
® ® ® ® ®
Molikote
BR2 plus.
¡When the housing need to be repeinted,
pay attention that the flameproof joints rest
without traks of coating!
Inspection
¡The nationals regulations have to be
observed!
E.g. in Spain the inspections of the installations in
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical
Low Votage Regulation following the indications
stablished in IEC 60079-17.
¡We suggest a revision after every service!
¡When the inspections are in degree of
"Detailled" or "Closed", the luminaires
have to be disconnected from the main
conection!
Repairing
¡The nationals regulations have to be
observed. The tasks of repairing have to be
made by "qualified" personnel!
¡The reparation of the sealed part between
the collarand the glass have to be done by
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
are not authorized to repair this sealed
part!
¡All reparations have to be done without
voltage!
For repair electrical equipments in protection mode is
suggested follow the instructions indicated
in IEC 79-19.
Only use genuine
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Subject to alteration or supplement of this product
o
C
without any advertisement before.
Cooper Crouse-Hinds, S.A.
. The users
spare parts.
5

Publicité

loading