Humidity
The HRV has a relative humidity (RH) sensor. The humidity menu specifies at what RH the HRV will
boost to speed 3.

Filter

The HRV's filters require regular replacement depending on environmental conditions. The
replacement period is set in the Filter section during setup as are the checked and replaced dates.
In normal use filter check and replace messages will appear on the main screen after changing or
checking filters messages are cleared by pressing and holding [5 seconds] the QUICK BUTTON.

Boost Overrun

auramode
has separate timers for wet room and kitchen boost that controls the time the HRV
remains at speed 3 after all switches have been released.
Switches
The HRV has multiple switch inputs whose function can be programmed. SW1, 2 & 3 are volt free
switch inputs and LS1 & 2 are live switch inputs.
Switch Options
Kitchen Boost
Wet Room Boost
Kitchen
Commission
The Commission menu screen is used to program the
supply and extract fan speeds. When the menu screen is
selected the HRV fans will start to run at speed 2.
Use
&
to move between fan speeds the cursor
underlines the supply or extract speed l/s. Pressing the
highlights the speed l/s selected to be modified and
the HRV immediately switches to run supply and extract at
the corresponding speeds. Use the
speed l/s and
to save. When all the required fan speeds
have been configured navigate to the
exit the Commission menu to the
Use
and
to move between fan speeds - the cursor will highlight the supply or extract
speed. Press
to select the required speed - the HRV will begin running at the selected speed,
and modify the speed using
another speed or if all the required fan speeds have been set as required navigate to the SAVE
option to save all settings to memory and return to the SETUP menu.

Reset

Reset menu sets to the default values.
8
SummerBOOST Disable
Wet Room
SummerBoost
&
to modify the
SAVE
option to save &
SETUP
menu, the unit will return to
and
. When speed is correct press
Speed 1 Setback
Speed 4
►SAVE
Commission
SUPPLY
88
179
311
392
Commissioning screen
AUTO
operation.
and either select
EXTRACT
78
166
295
392