1.3 Wiring precautions
Always use a shielded cable for all low-voltage connections.
Always use a shielded cable for all high voltage connections.
For communication connections, always use a twisted-pair shielded cable.
Do not connect the shielding of low-voltage connections to the earthing block (PE).
Do not connect the shielding of communication links to the earthing block (PE).
The maximum length of the communication link shall not exceed 1200 metres.
Disconnect high-voltage connections from low-voltage connections and/or
communication connections to prevent interference.
If inductive loads such as magnetic switches etc. are connected to the equipment,
Schippers advises to disconnect these loads by placing an RC filter (100ohm + 100nF)
in parallel.