Drain Pump Kit
n Connection of drain hose at
indoor unit side
1. Insert the drain hose attached to the indoor unit
into the drain pipe connecting port of the indoor
unit's and into the drain pipe connecting port of
the Drain Pump Kit's drain pan.
In this time, insert the drain hose until it strikes
on the connecting port of the drain pipe.
2. Align the hose band attached to the indoor unit
with the end of pipe connecting port, and then
tighten it firmly.
3. Cut off to 6.3" × 7.9" (160mm × 200mm) the
thermal insulator 7.9" × 7.9" (200mm × 200mm)
for drain hose attached to the indoor unit.
Using it, lap the connecting section of drain
pan and drain hose without clearance, and
then tighten it with two banding bands attached
to the indoor unit so that thermal insulator does
not open.
Attached drain hose
Check the soft
hose is pushed
Indoor unit
in to the end of
drain pan
drain pan.
Align the attached hose bands with the end
of hose and then tighten it while turning the
knob to the side.
Lap insulator over the
connecting section of drain
pan and drain hose.
Drain hose
Banding
band
Hose band
Thermal insulator attached to indoor unit
(Cut to 6.3" × 7.9" (160mm × 200mm))
Drain Pump Kit
drain pan
Lap the one side of
the attached thermal
insulator on the other
side at the upper side.
9
n Connection of drain hose at
Drain Pump Kit side
1. Insert the drain hose attached to the Drain Pump
Kit into the connecting port of drain pipes at the
upper side of the Drain Pump Kit.
2. Align the hose band attached to the Drain Pump
Kit with the end of pipe connecting port, and
then tighten it firmly.
3. Fit the drain connecting thermal insulator
attached to the Drain Pump Kit to sheet metal at
the upper side of the Drain Pump Kit, and then
lap it covering the drain hose without clearance.
Fit the drain connecting thermal insulator to sheet
metal at the upper side of the Drain Pump Kit,
and then lap it without clearance.
Hard vinyl chloride
pipe VP-25
(Procured locally)
∗ When using the drain hose within 5.9" (150mm) or
less from the top face of the indoor unit, do not use
an elbow but connect the attached drain hose
directly, which was bent (with larger round as
possible as you can).
Installation Manual
Drain hose
(Attached to Drain Pump Kit)
Thermal insulator for drain
connecting section
(Attached to Drain Pump Kit)
Drain pipe
connecting port
Thermal insulating pipe
(Attached to Drain Pump Kit)
Thermal insulator for drain
connecting section
(Attached to Drain Pump Kit)
Hose band
(Attached to Drain Pump Kit)
Drain hose
(Attached to Drain Pump Kit)
Fit the thermal insulating pipe
to sheet metal at the upper side
of the Drain Pump Kit, and then
lap it without clearance.
English-8