Standard Recovery Operation - JB INDUSTRIES F6-DP Instructions D'utilisation

Machine de récupération de fluides frigorigènes
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

STANDARD RECOVERY OPERATION

Connect all cables and hoses as described in Setup and Operation on page 8�
1
NOTE: Make sure all connections are tight, and that the cables and
hoses do not interfere with the recovery process (See Figure 1).
Figure 1 - Setup Procedure for Standard Refrigerant Recovery
2
Make sure the hose connecting the F6-DP to the recovery tank is attached to
the LIQUID port (LP)�
3
OPEN the LP valve on the tank — Keep the VAPOR port CLOSED�
4
Rotate the INLET valve (V1) to CLOSE�
Set the PURGE/RECOVER valve (V2) to the RECOVER position�
5
6
Slowly rotate the LIQUID valve on the MANIFOLD gauge to OPEN� Make sure there
are no leaks�
Turn on F6-DP�
7
Monitor the inlet pressure (LP, Low Pressure Gauge) and slowly rotate the INLET valve
8
(V1) to OPEN�
The compressor may emit a knocking sound if the F6-DP attempts to recover a
significant amount of liquid� To prevent damage to the compressor, throttle the LIQUID
valve on the MANIFOLD gauge set, or the F6-DP INLET valve (V1)�
9
Once the liquid has been recovered, transfer the remaining vapor; rotate the INLET
valve (V1) to OPEN� Make sure the LIQUID and VAPOR valves on the MANIFOLD
gauge are OPEN�
F6-DP OPERATING MANUAL
JB INDUSTRIES
9

Publicité

Table des Matières

Dépannage

loading

Table des Matières