Horizontal Mounting

The unit can be installed on a platform or suspended from rails as
shown below. The rails must run the length of the unit and be of
sufficient strength to support the weight of the unit and connected
ductwork. Vibration isolation is recommended for horizontal
installations. Some jurisdictions may require an auxiliary drain pan
be mounted under the unit. Always follow local or national code
requirements.
Platform Mounting
Suspended Mounting
Specifications are subject to change without notice.

10. Air filter

A washable (reusable) air filter is provided with the air handler unit.
The filter can be installed once the unit has been removed from its
packaging. It is recommended the air filter be cleaned once per
month.
The pressure drop is to be determined by the installing contractor
based on the overall static pressure performance of the system
including supply and return ductwork sizing. The factory static
pressure performance is 0.50" esp. A field selectable 0.30 and 0.80
esp. is available. See instructions for changing to 0.30 or 0.80 esp in
the electrical section (13.4.).
AUXILLARY
DRAIN PAN
17
FILTER
© 2022 Mitsubishi Electric US, Inc.