Les langues disponibles

Les langues disponibles

3-3. Audible Alarm

Description
UPS status
Bypass mode
Battery mode
Fault mode
Warning
Overload
Low battery
Battery disconnected
Over charge
EPO enable
Fan failure/Over temperature
Charger failure
Input phase dislocation
Input voltage unbalanced
Input phase lost
Fault
Bus start failure
Bus over
Bus under
Bus unbalance
Inverter soft start failure
High Inverter voltage
Low Inverter voltage
Inverter output short-circuited
Battery SCR short-circuited
Over temperature
Overload

3-4. UPS Operation

1. Switch on the UPS with utility power supply (in AC mode)
1)
Once the power supply has been correctly connected, set the breaker of the battery pack to the
"ON" position (step only available for long-run model). Then set the input breaker to the "ON"
position. The fan is now running and the UPS supplies power to the loads via the bypass. The
UPS is operating in Bypass mode.
NOTE 1: When the UPS is in Bypass mode, the output voltage will be directly supplied by the
utility power after you switch on the input breaker. In Bypass mode, the load is not protected by the
UPS. To protect your valuable devices, you should switch on the UPS. Refer to next step.
Press and hold the "ON" button for 1s to switch on the UPS and the buzzer will beep once.
2)
3)
A few seconds later, the UPS will switch to AC mode. If the utility power is unusual, the UPS will
operate in Battery mode without interruption.
NOTE 2: If the UPS is shut down in Battery mode automatically and the utility power is restored, the
UPS will start over and switch to AC mode automatically. When the UPS is running in battery, it will
shut down automatically in Battery mode. When the utility power is restored, the UPS will auto restart.
2. Switch on the UPS without the utility power supply (in Battery mode)
Make sure that the breaker of the battery pack is in the "ON" position (only for the long-run model).
1)
Press and hold the "ON" button for 0.5s to switch on the UPS, and the buzzer will beep once.
2)
3)
A few seconds later, the UPS will run in Battery mode.
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
43
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 11 16 AA XX 201 07
Buzzer status
Beeping once every 2 minutes
Beeping once every 4 seconds
Beeping continuously
Beeping twice every second
Beeping once every second
Beeping continuously
Muted
Yes
No
Yes