STEINEL IS 140-2 Z-Wave Mode D'emploi page 28

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

If a transition ( even with zero change ) with a non-default duration is to be pro-
cessed, the transition cannot be interrupted by any motion event in any case.
Lamp is switched off and remains so until any new motion event
0
( local or remote ) is received.
Lamp is switched off and remains so until after a specified timeout
once a new motion event ( local or remote ) is received.
Timeout:
1 - 209
1..100 – 1 second ( 1 ) to 100 seconds ( 100 ) in 1-second resolution
101..200 – 1 minute ( 101 ) to 100 minutes ( 200 ) 1-minute resolution
201..209 – 1 hour ( 201 ) to 9 hours ( 209 ) in 1-hour resolution
210 - 254
Reserved
Lamp is switched off for TIME ( cfg 1 ). It does not wait for a
255
motion event and works normally via current motion evaluation.
On behaviour ( timeout ):
Parameter Number
11 ( ON_BEHAVIOUR )
Behaviour after BASIC ON ( and similar commands ).
If a transition ( even with zero change ) with a non-default duration is to be pro-
cessed, the transition cannot be interrupted by any motion event in any case.
Lamp is switched on and remains so until any new motion event
( local or remote ) is received. It then works normally via current motion
evaluation.
0
Notice – during the day, this mode cannot be ended remotely due to
motion events not being transmitted – only via local motion sensor if
enabled.
Lamp is switched on and remains so until after a specified timeout
once a new motion event ( local or remote ) is received. It then works
normally via current motion evaluation.
Timeout:
1..100 – 1 second ( 1 ) to 100 seconds ( 100 ) in 1-second resolution
1 -209
101..200 – 1 minute ( 101 ) to 100 minutes ( 200 ) in 1-minute resolution
201..209 – 1 hour ( 201 ) to 9 hours ( 209 ) in 1-hour resolution
Notice – during the day, this mode cannot be ended remotely due to
motion events not being transmitted – only via local motion sensor if
enabled.
210 - 254
Reserve
Lamp is switched on for TIME ( cfg 1 ). It does not wait for a motion
255
event and works normally via current motion evaluation.
Size
Range
Default
2
0 – 209, 255
255
- 54 -
On behavior time over ( timeout ):
Parameter Number
12 ( ON_TIME_OVER )
Time limit to stop waiting for motion after timeout of ON_BEHAVIOUR or
OFF_ON_BEHAVIOUR ( 0-209 ) to prevent staying ON forever when is no motion.
0
Stop waiting just after timeout.
1..100 – 1 second ( 1 ) to 100 seconds ( 100 ) in 1-second resolution
1 -209
101..200 – 1 minute ( 101 ) to 100 minutes ( 200 ) in 1-minute resolution
201..209 – 1 hour ( 201 ) to 9 hours ( 209 ) in 1-hour resolution
210 - 254
Reserve
255
Never stop waiting before motion.
Sequence On-Off behavior ( timeout ):
Parameter Number
13 ( ON_OFF_BEHAVIOR )
Behaviour after after a rapid sequence of BASIC ON and BASIC OFF
commands.
The intention is to use a much longer timeout value than the time after a single
ON command which should then be followed by a short timeout value.
The behaviour is the same as for parameter 10 ( OFF_LOCAL_DISABLE ) except:
255 – device ignores ON - OFF sequence and uses OFF behavior
Sequence Off-On behavior ( timeout ):
Parameter Number
14 ( OFF_ON_BEHAVIOUR )
Behaviour after after a rapid sequence of BASIC OFF and BASIC ON
commands.
The intention is to use a much longer timeout value than the time after a single
OFF command which should then be followed by a short timeout value.
The behaviour is the same as for parameter 11 ( ON_LOCAL_DISABLE ) butex-
cept: 255 – device ignores OFF - ON sequence and uses ON behaviour.
Size
Range
Default
2
0 – 209, 255
204
Size
Range
Default
2
0 – 209, 255
204
Size
Range
Default
2
0 – 209, 255
204
- 55 -

Publicité

Table des Matières
loading