it
•
(total reversal)= activating this function, if the motors encounter an obstacle
GB
in the opening phase, they reverse the motion and close the gate completely. In
the closing phase, if they encounter an obstacle, the movement is reversed and
the gate opens completely. If the function has not been activated, in the opening
phase, the motors stop if they encounter obstacles while in the closing phase they
reverse motion by 30cm before stopping.
it=0
function not enabled.
it=1
function enabled.
2b
•
(two safety ribs)= Operates with two safety ribs 8k2 connected in parallel.
2b=0
function not enabled.
2b=1
function enabled.
cf
•
(operation of the fi xed code integrated receiver)=
rolling codes.
cf=1
receiver works with fi xed codes.
Functioning with receiver fi xed codes or rolling codes can also be seen on the
initial page of the display, where
f-00
functioning with fi xed code.
The receiver can memorise rolling codes type HCS300 STAGNOLI with billions
of combinations or fi xed codes type HT53200 with 13 bits or the fi xed part of a
rolling code (28 bit SN).
al
•
(alarm)= Alarm signalling that the gate has remained open. This function
activates the SCA output after 20 seconds have passed from the end of the time
regulated by
al=0
function not enabled.
al=1
function enabled.
te
•
(test)= A diagnostics test is carried out to check the integrity of the encoder
and amperometric sensors before each time the motors are started.
te=0
function not enabled.
te=1
function enabled.
Cancel
default parameter
•
functions and reset the factory settings, enter the menu cancel, go to
rameter
until the decision to reset all the parameters is confi rmed or the operation is can-
celled. The default parameters are:
rlch=20, sbat=5, v rl=3, fm1a=50, fm1c=50, fm2a=50, fm2c=50, tser=2,
fend=30, ca=1, ba=0, bp=0, cr=0, 2p=0, pl=0, sv=0, ar=0, re=0, 1m=0, en=1,
ss=0, ac=0, it=0, 2b=0, cf=0, al=0, te=0.
erase 1 transmitter
•
go to the wording
message
be cancelled. If the operation has been carried out correctly, the message
appear. If this has not been carried put correctly, the message
12
ttca
and the gate is still open.
= to cancel the regulation parameters and those of regulated
on the display and press ENTER. The message
= to cancel a transmitter code, enter the menu
erase 1 transmitter
PREMI.
(PRESS) will appear. Now press the key of the transmitter that must
r-00
indicates the rolling code functioning and
ttca=10, aped=70, sfaa=1, sfac=3, rlap=20,
on the display and press ENTER. The
cf=0
receiver works with
default pa-
RESE
is shown, it fl ashes
delete
ERR
will appear.
, then
OK
will