Gas Connection; Electrical Connection - Pitco Frialator SG 14 Manuel D'installation Et De Fonctionnement

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

c. Once the unit is in place, check and readjust the levelness as necessary.

GAS CONNECTION

Your fryer will give you peak performance when the gas supply line is of sufficient size to provide the correct gas flow.
The gas line must be installed to meet the local building codes or National Fuel Gas Code ANSI Z223.1 Latest Edition.
In Canada, install the fryer in accordance with CAN/CGA-B149.1 or .2 and local codes. Gas line sizing requirements
can be determined by your local gas company by referring to National Fuel Gas Code, Appendix C, Table C-4 (natural
gas) and Table C-16 (propane). The gas line needs to be large enough to supply the necessary amount of fuel to all
appliances without losing pressure to any appliance.
NEVER supply the fryer with a gas that is not indicated on the data plate. Using the incorrect gas type will
cause improper operation. If you need to convert the fryer to another type of fuel, contact your dealer.
Fuel Types - Each fryer is equipped to work with one type of fuel. The type of fuel with which the appliance is intended
to operate is stamped on the data plate attached to the inside of the door.
NEVER use an adaptor to make a smaller gas supply line fit the cooker connection.
This may not allow proper gas flow for optimum burner operation, resulting in poor
cooker performance.
Quick Disconnect Gas Connection
Gas fryers equipped with casters must be installed with connectors that comply with the Standard for Connectors for
Movable Gas Appliances, ANSI Z223.1 Latest Edition, and Addenda Z21.69A Latest Edition. This connection should
include a quick disconnect device that complies with the Standard for Quick Disconnect Devices for Use With Gas
Fuel , ANSI Z223.1 Latest Edition. When installing a quick disconnect you must also install a means for limiting the
movement of the fryer. This device will prevent the gas line or the quick disconnect from being strained. The
restraining device should be attached to the cooker on the back panel.
Fuel Supply Line Leak and Pressure Testing
The fuel supply system must be tested before the fryer is used. If the fuel line is going to be tested at a pressure greater
than (>)1/2 PSIG (3.45 kPa), make sure that the fryer is disconnected from the fuel line. If the fuel line is to be tested
at a pressure equal to or less than (<) 1/2 PSIG (3.45 kPa), the fryer can be connected but the unit's gas valve must be
shut. Test all gas line connections for leaks with a solution of soap and water when pressure is applied.

ELECTRICAL CONNECTION

The electrical service used by the fryer must comply with local codes. If there are no local codes that apply, refer to
the National Electrical Code (NEC), ANSI/NFPA 70 to install the service. In Canada refer to CSA Standard C22.1
and local codes. Wiring diagrams are provided inside the fryer control box. The power requirements for the fryer are
shown below.
Input Voltage
Current per fryer
Filter System
The fryer must be grounded in accordance with local code; if there is not a local code, comply with NEC ANSI/NFPA
No. 70-1990. It is advised that this power supply be plugged into a wall receptacle that is controlled by the ventilation
control. This will prevent the fryer from being operated without the ventilator on.
6
WARNING
NOTICE
North America
120 VAC, 60Hz
0.5 Amps
7.0 Amps
2
International
220 (or 240) VAC, 50Hz
0.5 Amps
4.0 Amps

Publicité

Table des Matières
loading

Produits Connexes pour Pitco Frialator SG 14

Table des Matières