PARAMETER 1100 = 4
[Thermostat]
230V
OUT 1
N
L
N
L
230 V
PUMP
In this mode, the device functions as a ge-
neric thermostat between a sensor con-
nected to input IN1 and a setpoint (target)
temperature.
If the IN1 temperature exceeds the setpoint
value (set via parameter 1130) by a cer-
tain number of degrees (set via parameter
1131), output OUT1 is activated.
Par.
Description
1110
IN1 temperature
reading
1130
Temperature set
1131
Hysteresis
16
OUT 2
OUT 3
IN 1
IN 2
N
L
N
L
SENSOR
Range
-20..150°C
0..130°C
0..30°C
PARAMETER 1100 = 5
[Timed output, in conjunction with a system
interface]
IN 3
BUS
230V
B
T
N
L
SOLAR HEATING
230 V
PUMP
SYSTEM ZONES
BOILER
In this mode, output OUT1 is powered in
line with a programmed schedule, which
can be set using the system interface (in-
dispensable for managing this function) as
follows:
Press ok > Complete menu > Hot water
settings > Free programming > Auxiliary
timer
Application example:
- by connecting a recirculation pump to
OUT1, it will be possible to operate it on a
timed basis (e.g. On in the daytime, Off at
night).
OUT 1
OUT 2
OUT 3
IN 1
N
L
N
L
N
L
SOLAR HEATING SYSTEM INTER-
IN 2
IN 3
BUS
B
T
FACE BOILER