(4) Set the system remote controller address with the rotary switches.
System remote controller upper case
CAUTION Addresses between 201 and 250 may be set with the system remote controller. The place of 100
is fixed to "2".
Rotary switch setting
01~50
• If an address other than those listed above is set, an address setting error occurs and "AdE" is displayed.
• The rotary switch is set to 01 when shipped from the factory.
(5) When used in conjunction with the master system controller (centralized controller), set the system
remote controller to "Slave" with the switch as shown in the diagram below.
• The switch is set to "Master" when shipped from the factory.
Master
Slave
(6) Connect this connector on the lower case to the connector CN1 on the upper case.
CAUTION • Connect firmly as shown below. The system will not operate unless these connections are
made.
• After connecting the wiring, ensure that the upper case does not hang off the cord as shown in
the diagram below at the right. This may result in a break in the cord, and thus cause problems
with operation.
• Always pass the cord through the hook to hold it in place.
Hook
Remote controller lower case
(7) Fitting the upper case.
First hook the upper case to the two upper claws and then fit it
as shown at right.
CAUTION
• Press the case until it snaps shut.
• A protective sheet has been affixed to the control panel.
Remove it before starting.
Rotary switch
× 10
Example : Address 208
Address
201~250
System remote controller upper case
Connect this to
Connector CN1
connector CN1
Remote controller upper case
× 1