Waeco AirCon Service VES100 Notice D'utilisation page 23

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 26
VES100
6.4
Recovering refrigerant
I
NOTE
 If the weight selected exceeds the total weight of refrigerant in
the gas bottle, the fault message "ERROR" is displayed.
 The weight of the bottle to be filled must not exceed 80 % of
the total quantity.
➤ Connect the gas bottle to a recovery system (fig. 6, page 4).
➤ Connect the refrigerant scale to the AC mains using the AC cable
(fig. 1 1, page 2).
➤ Connect the "Output" connection to the air conditioning service
station(fig. 2 2, page 2).
➤ Connect the gas bottle from which refrigerant is to be recovered to the
"Input" connection (fig. 2 1, page 2).
➤ Switch on the scale using the on/off switch (fig. 2 3, page 2).
➤ Place the filled gas bottle to be emptied on the scale.
➤ Wait until the scale has determined the current weight and displayed this.
➤ Press the "Recover" button (fig. 3 8, page 3).
➤ Enter the weight to be removed (min 50 g) using the numerical keys.
➤ Press the "Enter" button (fig. 3 6, page 3).
✓ The solenoid valve is opened and the refrigerant extracted.
The solenoid value closes when the selected quantity of refrigerant has
been charged.
The scale displays the remaining quantity of refrigerant in the filled
refrigerant bottle.
I
NOTE
 Press the "Enter" button fig. 3 6, page 3) to stop a process at
any time. After this, press the "Recover" button (fig. 3 8,
page 3), to return to the previous screen.
 If you want to end the charging process before the selected
quantity of refrigerant has been reached, then press the "0"
button. Press the "Enter" button (fig. 3 6, page 3) to exit the
mode.
EN
Use
23

Publicité

Table des Matières
loading

Table des Matières