5.
Adjust the water level. (See Nos. 7 & 8 in "Plumbing and Setting the Water
Level", pgs. 11 & 12.)
6.
Slide the flanges of the humidifier reservoir into the mounting bracket.
7.
Secure the humidifier to the duct with the screws provided.
Figure 5—Option C:
Duct Center Mount
Figure 6—Mounting Bracket
3.
Attach the mounting bracket to the ductwork with sheet metal screws.
4.
Adjust the water level. (See Nos. 7 & 8 in "Plumbing and Setting the Water
Level", pgs. 11 & 12.)
5.
Slide the flanges of the humidifier reservoir into the mounting bracket.
6.
Secure the humidifier to the duct with the screws provided.
NOTE: See separate wiring instruction manual, "Wiring Instructions for High-
Capacity Steam Humidifiers".
Option C requires duct reinforcement
to hold the humidifier securely in place.
dANgER: Wear safety glasses when
cutting or drilling. Do not cut or drill into
any air conditioning components or electri-
cal enclosures during installation. Electro-
cution is possible if you come in contact
with a live electrical wire; blindness can
occur if refrigerant contacts your eyes.
To install (Option C:)
1.
Place the mounting bracket (provided)
at the selected location on the bottom
of the duct.
2.
Use a marker to trace around the inside
of the mounting bracket. Cut out the
duct opening.
CAuTION: DO NOT attach the mount-
ing bracket before the hole in the duct-
work has been cut.