English – Instructions
Attention: This device shall only be connected to power supplies compliant
to EN60950-1, chapter 2.5 ("limited power source").
Risk of damage to the device
Use the device only indoors and in dry environments.
Do not expose it to dripping or splashing water.
Do not let the contact areas of the board get dusty and do not touch
them with your bare hands.
EC Declaration of Conformity
Hereby, Vanderbilt International (IRL) Ltd declares that this equipment type, is in
compliance with all relevant EU Directives for CE marking. From 20/04/2016 it is in
compliance with Directive 2014/30/EU (Electromagnetic Compatibility Directive).
The full text of the EU declaration of conformity is available at:
http://pcd.vanderbiltindustries.com/doc/SPC

Product description

The SPCE110 is a universal key switch expander. It is used in combination with
SPCK620/623 or SPCE120 to release them for operation. The function of the
LEDs and key positions can be freely defined via the control unit. The expander
features also a buzzer for acoustic notification and a freely programmable relay
t.
outpu
Product overview
See Fig. 1: Product overview
Lugs holding the PCB
1
Buzzer
2
Rotary switches
3
Fixing screws for PCB
4
Jumper J4 (NO / NC selection for relay)
5
X-BUS termination jumper (fitted by default)
6
Relay
7
Tamper switch
8
Jumper J3 (not used, open)
9
Breakout
10
Breakout
11
Holes for fastening
12
Lugs
13
Corrugated-head screw for back tamper contact
14
Screw terminal
15
Assembly
Open housing
1. Loosen screws with several turns (Figure 2).
2. Use a screwdriver to press the snap-fits down (Figure 2 item 1) and slightly lift
the top of the housing.
3. Lift the housing top approx. 1 cm and push up (Figure 3).
Wire the device
1. Carefully bore open the breakout point (Figure 1 item 10 or 11) and pull the
wire through.
2. Connect the individual wires to the screw terminals.
See Fig. 1, item 15: Contact pins
Contact pin Abbreviation
1
NO / NC
2
COM
3
1A
4
1B
5
2A
6
2B
7
0V
8
+12
9
SCL
10
SDA
Configuration of the relay output
The relay output can be configured to be normally open or normally closed. This
configuration has to be done via the Jumper J4.
Jumper in upper position = normally open
Jumper in lower position = normally closed
Mount the bottom of the housing
Function
Relay
Relay
X-BUS
X-BUS
X-BUS
X-BUS
Power supply negative
Power supply positive
Not used
Not used
Only mount the device on sub-surfaces made of stable materials.
1. Mark the locations for 3 holes for the fastening screws (Figure 1 item 12) and
hole for the corrugated-head screw (Figure 1 item 14).
2. Drill the holes and attach the bottom of the housing with the screws.
Close the top of the housing
1. Hang the top of the housing on the top of the bottom of the housing and press
towards the back.
 The two snap-fits on the lower part of the bottom of the housing snap in.
2. Tighten the two screws on the bottom side and seal them using the supplied
seals (Figure 5).
Wiring the X-BUS interface
The X-BUS interface provides connection of expanders and keypads to the SPC
controller. The X-BUS can be wired in a number of different configurations
depending on the installation requirements.
NOTE: Maximum System cable length = number of Expanders and Keypads in the
system x maximum distance for cable type.
Cable type
CQR standard alarm cable
UTP category: 5 (solid core)
Belden 9829
IYSTY 2 x 2 x 0.6 (min)
Fig. 6 shows the wiring of the X-BUS to an expander/controller and the following
expander/controller in Spur Configuration. Terminals 3A/3B and 4A/4B (if available
for this module) are only used for using a branch wiring technique. If using a Spur
configuration, the last keypad is not wired back to the controller.
See Fig. 4: Wiring of expanders
1
SPC controller
2
Previous expander
3
SPCE110
4
Next expander
Please refer to SPC Configuration Manual of connected controller for further wiring
instructions, shielding, specifications and limitations.
X-BUS addressing
For addressing, reconfiguration, device location, monitoring, editing of names, X-
BUS type of communication, failure timer please refer to SPC Configuration
Manual.
Overview of installation tools
See Fig. 6: Overview of installation tools
Connection element
1
Horizontal end piece
2
Vertical end piece
3
Middle piece (only for mounting 1 SPCK620/623 with 2 modules)
4
Installation with a keypad or other modules
Vertical installation (e.g. 2 modules, Fig. 7)
1. Place 2 horizontal end pieces (Fig. 6 item 2) on the end of a connection
element (Fig. 6 item 1)
2. Snap the connection element into the connection pins of the device so that the
arrow on the connection element is pointing up (Fig. 7).
Horizontal installation (e.g. 1 module with SPCK620/623, Fig. 8)
1. Place 2 vertical end pieces (Fig. 6 item 3) on the ends of a connection element
(Fig. Fig. 6 item 1)
2. Snap the connection element with the oval holes towards the center onto the
connection pins of the device (Fig. 8)
Horizontal and vertical installation (e.g. SPCK620/623 and 2 modules,
Fig. 9)
1. Apply a vertical end piece to the 2 connection elements on the end with the
round holes (Fig. 6 item 3).
2. Snap in the 2 vertical connection elements with the oval holes towards the
center on the SPCK620/623.
3. Place 1 horizontal end piece (Fig. Fig. 6 item 1) on the right end and a middle
piece (Fig. Fig. 6
item 4) on the left end of a connection element.
4. Snap the horizontal connection element onto the connection pins of the device
so that the arrow is pointing up (Fig. 9).
5. Snap the vertical connection elements of the SPCK onto the connection pins of
the two connected modules.

Technical data

LED indicators
Programmable key input
Number of on-board relays
Distance
200 m
400 m
400 m
400 m
2 tri-color LEDs
3 key positions
(2-0-1 in 90° steps, cylinder type KABA1008C)
1 (single-pole changeover, 30 VDC / max. 1 A
resistive switching current)