100920 AD500 Install instruct
S S y y s s t t e e m m O O p p t t i i o o n n s s
For most installations the factory settings for the system will be appropriate. To
customize the system, use the following programming steps.
Keypad Lockout Count
The system counts the number of invalid entry codes entered at the local or
remote keypad. The factory settings for the lockout count is five. The lockout value.
can be from two to seven.
1. If not already in Programming Mode, connect by telephone or use the
local keypad. Enter the master password and access programming.
2. Press:
3. Enter the number for the lockout count (2-7).
4. Press:
5. Exit Programming Mode if all programming is complete.
Relay Activation Time
The factory setting will cause the relays to activate for two seconds. The
activation time can be set from 1-60 seconds to accommodate different types of
access control devices.
1. If not already in Programming Mode, connect by telephone or use the
local keypad. Enter the master password and access programming.
2. Press:
3. Choose which relay to set.
• Enter 1 for Relay Channel "A"
• Enter 2 for Relay Channel "B"
4. Press:
5. Enter the number of seconds for activation (1-60).
6. Press:
7. Exit programming Mode if all programming is complete.
Relay Channel "B" Function
Relay Channel "B" is normally used to control a second access device.
Alternately, Relay Channel "B" can be used for alarm contact shunting, obstacle
sensing output, or triggering audible alarms.
1. If not already in Programming Mode, connect by telephone or use the
local keypad. Enter the master password and access programming.
2. Press:
3. Enter a number for the Relay Channel "B" function:
• Enter 0 for normal access control.
• Enter 1 for Alarm Contract Contact Shunt (Relay "B" will activate when Relay
"A" activates.
• Enter 3 for triggering audible alarms on specific conditions.
4. Press:
5. If any number but 3 was entered above, skip to Step #8.
6. Enter the audible alarm option:
• Enter 1 for forced entry activation (activates if the sensing input is set for
Door Sense and detects an open access portal condition without access
being granted by the system).
• Enter 2 for door/gate ajar activation (activates if the sensing input is set for
Door Sense and still detects an open access portal condition one minute
after access was granted by system).
• Enter 3 for activation during local or remote keypad lockout.
7. Press:
8. Exit programming Mode if all programming is complete.
1/14/06
10:39 AM
Page 17
KEYPAD LOCKOUT COUNT
51 #COUNT#
COUNT = NUMBER 92-70 OF INCORRECT
ENTRIES REQUIRED FOR LOCKOUT
FACTORY SETTING: 5 TRIES
RELAY ACTIVATION TIME
52 #RELAY#SECONDS#
RELAY = 1 FOR RELAY CHANNEL "A"
RELAY = 2 FOR RELAY CHANNEL "B"
SECONDS = ACTIVATION TIME (1-60 SECONDS)
FACTORY SETTING: 2 SECONDS
RELAY CHANNEL "B" FUNCTION
53 #FUNCTION#ALARM#
FUNCTION = 0 FOR NORMAL ACCESS CONTROL
FUNCTION = 1 FOR ALARM SHUNT
FUNCTION = 3 ALARM ON CONDITION
ALARM = 1 FOR ACTIVATE ON FORCED ENTRY
ALARM = 2 FOR ACTIVATE ON DOOR OR GATE AJAR
ALARM = 3 FOR ACTIVATE ON KEYPAD LOCKOUT
FACTORY SETTING: 2 SECONDS
PPN 51
PPN 52
PPN 53
17