Output variable
Output
Modes min / max (changeover by electrical connection)
Ʋ Max.
Ʋ Min.
Voltage supply
Operating voltage
Power consumption
Load current
Ʋ Min.
Ʋ Max.
Electromechanical data
Valve plug ISO 4400
Ʋ Wire cross-section
Ʋ Outer cable diameter
Valve plug ISO 4400 with IDC method of termination
Ʋ Wire cross-section
Ʋ Single-wire diameter
Ʋ Wire diameter
Ʋ Outer cable diameter
Ʋ Connection frequency
Electrical protective measures
Protection rating
Ʋ Valve plug ISO 4400
Ʋ Valve plug ISO 4400 with IDC method
of termination
Overvoltage category
Protection class
LEVEL SWITCH 8110 • - contactless electronic switch
Contactless electronic switch
Max. detection or overflow/overfill protection
Min. detection or dry run protection
20 ... 253 V AC/DC
max. 0.5 W
10 mA
250 mA
1.5 mm² (0.06 in²)
4.5 ... 7 mm (0.18 ... 0.28 in)
for wire cross-section of 0.5 ... 1 mm² (0.02 ... 0.04 in²)
> 0.1 mm (0.004 in)
1.6 ... 2 mm² (0.06 ... 0.08 in²)
5.5 ... 8 mm (0.22 ... 0.31 in)
10 x (on the same cross-section)
IP 65
IP 67
III
I
9 Supplement