3.- Equipment description
Alarm station
Mute/reset button
Mutes the alarm or deletes saved alarms
Pre-alarm jumper
It allows activating pre-alarm detection.
Before using this option, make sure that
regulations allow for only two alarm levels.
Pre-alarm enabled
Pre-alarm disabled
When using the ammoniac (AKO-52213) or CO (AKO-52215) detector, the pre-alarm must be
enabled.
Gas detector AKO-52211/12/13/14
Delay switch
It delays the activation of alarms detected in the station.
The detector status indicators will indicate the alarms and
pre-alarms immediately, without taking into account the
delays.
ON
Without delay*
ON
ON
60 sec.
IMPORTANT: The delay configuration should be carried out with the station's power supply
disconnected, as if not it will not work.
Gas detector AKO-52215
Response selector
It defines the detector's type of response and affects both
the reading shown on the indicator and the activation of
the alarms.
Immediate response: The detector reacts
ON
depending on the last reading obtained.*
Delayed response: The detector reacts
ON
ON
depending on the average value of the
last 11 readings.
The interval between readings is 15 seconds, regardless of the position of the selector.
VISUAL ALARM
DETECTOR STATUS
POWER SUPPLY STATUS
ACOUSTIC ALARM
PRE-ALARM JUMPER
MUTE/RESET BUTTON
ON
ON
30 sec.
ON
ON
120 sec.
14
2
STATUS INDICATORS
DELAY SWITCH
STATUS INDICATORS
RESPONSE
SELECTOR
CO CONCENTRATION INDICATOR
2
IN PARTS PER MILLION (ppm)
*Default value
1 2 5 8
*Default value