Terminal plan
Escape door control terminal 1340-10 (24 V)
+24V
+24V
K9
F2
+24V
K10
0,1AT
K4
F1
EMERGENCY OPEN switch
1AT
X1
1 2 3 4 5
6 7
8 9 10
X1.3
X1.4
Door monitoring contact necessary
in the models 827, 828, 829, 3150
X1:
5
6
8
9 10
7
+
-
1 2
4
5
6
3
Holding magnet 828
X1:
5
6
7
8
9
1 2
4
5
6
3
1 holding magnet 829 or 2x holding magnet 828
7 8 9 10
X1: 5
Dx
Dx
2 holding magnets 827
7 8
X1: 5
9 10
rd bl
gn ye gr
Electric panic
opener 3150
X1: 3 4
5
7 8 9 10
Escape
Monitoring
Armature
door lock
contact
contact
release 331
18
Operating voltage
Relais K9, K10
24VDC ±15%
Current consumption:
max. 40mA
+24V
X2
11 12 13 14 15 16 17 18 19 20
2
8 4
5 6 7
1
rd
gn ye
Central indicator panel 725
*) If no fire alarm system
is provided: Connect terminal 1
to terminal 19 and
terminal 2 to terminal 18.
10
4
1 2
5
3
6
For model 827, observe:
Connect spark suppression diode Dx
to the terminal of the holding magnet as
drawn:
Type 1N4007
=
Caution!
Check that connections are correctly executed.
Incorrectly connected systems result in
forfeiture of guarantee cover.
Observe the valid VDE regulations and the
stipulations of your local electricity board.
Fuse F2 is only necessary with model 828 and 829.
With all other models fuse F2 has to be removed!
Control conductors max. 100 m in length,
minimum cross-section dia. 0.6.
Conductors to the power supply
unit and locking element: max. length 300 m.
The conductor cross-section must be gauged
so that a voltage of 24 V is guaranteed at the
locking element.
+24V
K9
K10
Fire alarm
(2)
system *)
+24V
(1)
With externally
supplied voltage:
24 V ± 15%