Escape Door Control Terminal 1340; Installation - EFF EFF 1340-10 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

english
The compact-design effeff escape door control terminal
1340-10(11) is fitted with a central control circuit which triggers 1
door or 2 locking elements. The effeff escape door control terminal
has its own built-in power supply unit which must be fed with 24 VDC
stabilized direct voltage supply provided at the installation site.
Used as a central control system for the 3 basic effeff escape door
systems, it is therefore possible to achieve extremely compact
installation. Three different normally open locking elements permit
maximum scope of application.
Basic system A

Escape door control terminal 1340-10(11)

Door contact 10365
Door locking element 827-../828-../829-..
Basic system B
Escape door control terminal 1340-10(11)
Door contact 10400
Door locking element electric panic opener 3150
Basic system C
Escape door control terminal 1340-10(11)
Locking element
Electric escape door lock release 331 RR AKRR
with matching latch bolt 807
The above basic escape door control systems conform to building
regulations governing electrical locking devices on doors in escape
routes.
The control terminal 1340-10(11) forms the actual switching,
control and monitoring element of these three decentrally installed
basic systems. Operating statuses are indicated by 3 pilot lamps.
An integrated emergency switch effects immediate unlocking of
the locking element.

Installation

effeff escape door control systems must be installed correctly in
compliance with the valid „Building regulations governing electrical
locking device on doors in escape routes". The provisions of special
codes of building practice must also be observed precisely.
When installing the system, the locally applicable electricity board
and electrical engineering association regulations must be followed.
Connect the control terminal and external appliances in accordance
with the terminal plan. We recommend running a separate cable to
the locking element (induction on energising the coil).
To ensure electro-magnetic compatibility, only lay shielded
conductors. In buildings subject to strong magnetic or disturbing
fields, we recommend using multiple-shielded conductors, also to
the locking element.
Before switching on, ensure a voltage supply of 24 VDC (stabilized
direct current).
12