Default - Factory Settings - Macurco CD-6H Manuel D'instructions

Masquer les pouces Voir aussi pour CD-6H:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Macurco CD-xx H/MC Manual
2. Connect the CD-6H/MC to Class 2 power supply only. It is suggested to use a dedicated transformer for powering the
unit or units because of possible interferences from other devices on the same power supply.
3. Connect the CD-6H/MC to the control cables with terminal plugs. When making connections, make sure the power is
de-energized.
4. There are two terminals for Power: 12 to 24 VAC or 12 to 32 VDC, with no polarity preference.
5. There are two terminals for the dry alarm relay contacts, again with no polarity preference. The alarm relay can switch
up to 0.5 A 120 V, or 60 VA. The alarm relay is activated if gas reaches or exceeds the alarm settings. See section
Default – Factory Settings
6. The alarm relay can be configured to normally open (default) (N.O.) or normally closed (N.C.) and will activate if the gas
concentration exceeds alarm set point. It will deactivate once the gas concentration drops below the alarm set point.
Note that the "disable" setting will cause the alarm relay not to engage at all.
7. The dry contact, SPDT fan relay has three terminals. The common (COM.), normally open (N.O.) and the normally
closed (N.C.) contact. The fan relay can switch up to 5.0 A up to 240 VAC. See section
these User Instructions for details on relay settings.
8. The Fan Relay can be configured for latching or non-latching (default) when activated (when the gas concentration
exceeds fan relay setpoint). Once latched in, power will need to be interrupted or the "TEST" button pressed to un-
latch the relay condition.
9. The Fan Relay will engage if the fan setting Carbon Dioxide concentration is exceeded for longer than the Fan Relay
Delay time. Unless it is configured for latching, the fan relay will disengage once both conditions have been met:
Carbon Dioxide concentration has dropped below fan setting
Fan Relay Runtime has been exceeded
Note that the "disable" fan setting will cause the fan relay to not engage. The fan relay will engage in trouble fault
condition (if the Trouble Fan Setting Option is set to "ON") and will disengage once trouble fault condition is cleared.
10. The Current Loop is 4 mA in clean air and 4-20 mA for 0-5000 ppm CO
REV – 1.2
of this User manual for details on relay settings.
U 3 1 T
Figure 3-1 6-Series 4-20 mA Output diagram
[34-2900-0510-8]
4 .5 Default – Factory Settings
3 1 T
2
P
4 .5
3 1 T U
of
3 1 T
8 |
P a g e

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cd-6mcCd-12hCd-12mc

Table des Matières