Inside pipe diameter
Setting the flow monitor to the selected pipe size.
Three settings are possible:
Enhanced functions
This menu item contains a submenu with additional parameters.
You can access these parameters by pressing the SET button
briefly.
Min-Max memory for flow rate:
• HI: displays the highest measured flow range
• Lo: displays the lowest measured flow range
Erase the memory:
- Press the "Mode/Enter" button until HI or Lo is displayed.
- Press the "Set" button and keep it pressed until "- - -" is
displayed.
- Then press the "Mode/Enter" button briefly.
It is recommended to erase the memory as soon as the unit starts
working under normal operating conditions.
Customer-specific calibration (explanation
If the function is active, the current flow value is displayed.
- Press the SET button to set the requested value
(scrolling by holding pressed; incremental by pressing briefly).
- Acknowledge with the Mode/Enter button.
After calibration the calibration indicator is displayed at the upper
left corner.
Calibration is only possible for values > 25% of the final value of
the measuring range. For smaller values Lo is displayed, the set-
ting of the parameter is disabled.
Setting range: -40% ...+40% of the final value of the measuring
range;
max. value displayed: final value of the measuring range + 20%.
Calibration reset
- Press the "Mode/Enter" button until CAr is displayed.
- Press the "Set" button and keep it pressed until "- - -" is
displayed.
- Then press the "Mode/Enter" button briefly.
The calibration set by CGA is reset; the calibration indicator no
longer lights.
15, 19, 24.
page 35)
31