Technical information / Functioning / Parameters
Adjustable parameters
Switch-on point 1 / 2
Upper limit value at which the output changes its switching
status.
SP2 is active only if OU2 = Hno, Hnc, Fno or Fnc.
Switch-off point 1 / 2
Lower limit value at which the output changes its switching
status.
rPx is always lower than SPx. The unit only accepts values which
are lower than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automati-
cally reduced: rPx is set to the minimum setting value (0.0).
rP2 is active only if OU2 = Hno, Hnc, Fno or Fnc
Setting range for SPx / rPx: → page 59.
Configuration of output 1
4 switching functions can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
Configuration of output 2
4 switching functions and 2 analog signals can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
- I = analog output 4 ... 20 mA
- U = analog output 0 ... 10 V
Lower end of analog output
Measured value for which the output signal is 4 mA / 0 V.
ASP is active only if OU2 = I or U.
Upper end of analog output
Measured value for which the output signal is 20 mA / 10 V.
Minimum distance between ASP and AEP = 40%.
AEP is active only if OU2 = I or U.
Setting range for ASP / AEP: → page 59.