tipalo CO
Actual value alarm A1
Alarm threshold
120 ppm
Hysteresis
Actual value alarm A2
Alarm threshold
120 ppm
Hysteresis
Actual value alarm A3
Alarm threshold
120 ppm
Hysteresis
Actual value alarm A4
Alarm threshold
120 ppm
Hysteresis
Mean value alarm A1
Alarm threshold
Hysteresis
Mean value alarm A2
Alarm threshold
Hysteresis
Mean value alarm A3
Alarm threshold
Hysteresis
Mean value alarm A4
Alarm threshold
Hysteresis
Histereza npr. 10 ppm pri mejni vrednosti npr. 100 ppm pomeni, da se alarm nastavi na 100 ppm in ponastavi, če je pod 90 ppm.
1)
Prednastavitev v skladu z VDI 2053 (2004)
2)
Za VarioGard 3200 CAT in VarioGard 3300 IR Ex
Dräger VarioGard
Merilno
Merilno
Merilno
1)
tipalo NH
tipalo O
3
50 ppm
20 vol. %
5 ppm
5 ppm
0,2 vol. %
200 ppm
19 vol. %
5 ppm
20 ppm
0,2 vol. %
500 ppm
18 vol. %
5 ppm
50 ppm
0,2 vol. %
1000 ppm
17 vol. %
5 ppm
100 ppm
0,2 vol. %
20 ppm
1200 ppm
0 vol. %
4 ppm
0 ppm
0 vol. %
40 ppm
1200 ppm
0 vol. %
8 ppm
0 ppm
0 vol. %
60 ppm
1200 ppm
0 vol. %
10 ppm
0 ppm
0 vol. %
60 ppm
1200 ppm
0 vol. %
10 ppm
0 ppm
0 vol. %
Merilno
Merilno
tipalo NO
tipalo NO
2
2
10 ppm
1 ppm
3 ppm
0,1 ppm
15 ppm
2 ppm
3 ppm
0,2 ppm
20 ppm
3 ppm
3 ppm
0,3 ppm
20 ppm
5 ppm
3 ppm
0,5 ppm
50 ppm
1 ppm
5 ppm
0,1 ppm
50 ppm
2 ppm
5 ppm
0,2 ppm
50 ppm
3 ppm
5 ppm
0,3 ppm
50 ppm
5 ppm
5 ppm
0,5 ppm
Konfiguracija
Merilno
Merilno
2)
2)
tipalo CH
tipalo LPG
4
10 %LEL
10 %LEL
5 %LEL
5 %LEL
20 %LEL
20 %LEL
5 %LEL
5 %LEL
40 %LEL
40 %LEL
5 %LEL
5 %LEL
40 %LEL
40 %LEL
5 %LEL
5 %LEL
40 %LEL
40 %LEL
3 %LEL
3 %LEL
80 %LEL
80 %LEL
3 %LEL
3 %LEL
100 %LEL
100 %LEL
3 %LEL
3 %LEL
100 %LEL
100 %LEL
3 %LEL
3 %LEL
Merilno
tipalo CO
2
0,5 vol. %
500 ppm
1 vol. %
500 ppm
2 vol. %
500 ppm
3 vol. %
500 ppm
1 vol. %
500 ppm
1 vol. %
500 ppm
3 vol. %
500 ppm
3 vol. %
500 ppm
233