Activating and configuring an integral proportional algorithm
I
J
Cycle length
Prog.
(minutes)
P1
10
P2
5
P3
20
P4
from 5 to 40 from 1 to 5
TA350
Minimum ON
Proportional
time (minutes)
band
1
1.5 °C
1
1.5 °C
2
1.5 °C
from 1 °C to 3 °C
Use the
buttons to set the differential
value at a value between 0 °C and 0.9 °C H.
By setting the differential to 0 °C, during
operation, a minimum switching on/off time
of 1 minute is respected, regardless of the
detected room temperature.
Press button P to exit programming.
When the differential is not active
) F, press button P to access
(
the section in which it is possible to select
one of the integral proportional programs
available I.
Use the
buttons to choose the desired
program from: P1, P2, P3, J (see graph K
and table); press button P to confirm your
choice and end programming.
Type of system
Base for gas burner, fan coils, zone
valves, aluminium radiators
Electric radiators
Radiant or underfloor systems, cooling