CDVI A22K Mode D'emploi page 36

Masquer les pouces Voir aussi pour A22K:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Communication
LOCAL BUS
ETHERNET
Power Supply
AC Power
Frequency
Output
AC Terminal Fuse
Power Loss Indicator
Do Not Connect to a Receptacle Controlled by a Switch.
Other 24Vac, 75VA 50/60Hz UL/ULC certified transformer can be used.
On-Board Protection (All fuseless, auto-resume)
LK1, LK2
AUX
Battery
Power output specifications
Battery Backup
Battery Capacity
Charging Current
Low Battery @
Low Battery Restore @
Low Battery Cut-Off @
Power Outputs (+12Vdc)
Lock Output LK1
Lock Output LK2
Reader 1
Reader 2
Zone Inputs
LOCAL BUS
Outputs
RLY1, RLY2
36
A22K
Contrôleur 2 portes
RS485 @ 57600Baud supporting star and/or daisy chain topologies up to 4000ft (1220 meters)
10/100 Base-T, Auto Sensing, 100m(300ft)
120-240Vac
50Hz/60Hz
24Vdc, 2.5A
250Vac, 2.5 A, Time Lag, Slow Blow, Operating Temperature: -55
Yes (DC IN)
12Vdc @ 750mA
12Vdc @ 1A
Against reversal, short, current limited/monitored
One 12Vdc 7Ah rechargeable acid/lead or gel cell backup battery.
Europe: CDVI B7AH recommended). Ensure proper polarity.
250mA (default), 500mA, or 1A. Refer to the ATRIUM system manual to modify the battery
charging current .
11.8Vdc
12.2Vdc
10.5Vdc
Maximum Current 750mA each
Maximum Current 1000mA
Form C Relay, 5A @ 250Vac, 7A @ 125Vac, 7A @ 30Vdc
C to +125
C
o
o
EN