3.3
SPECIAL VENT INSTALLATIONS
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that
when fi nal grading is completed, the bottom air slot is located a minimum 12" above grade. The maximum
allowable vent length is 10'.
30" (762MM)
MINIMUM
3.3.2 CORNER TERMINATION
The maximum vent length for a corner installation is 20" (508mm) of horizontal run, in addition to the 45°
offset. In this case zero rise is acceptable. See illustrations below. It is required to maintain a 6"(152mm) rise.
12" (305MM)
MINIMUM
TO GRADE
30" (762MM)
6" (152.4mm)
RISE
MINIMUM
34 5/8"
(879MM)
20" (508mm)
MAXIMUM
13
EN
12" (305MM)
MINIMUM
TO GRADE
W415-1401 / D / 05.25.16