Installer setup
NOTE: The options below may not be available in all models.
Setup function
5 Heating cycle rate
(CPH: cycles/hour)
TH2110DV, TH1110DV
and TH1100DV
6 Auxiliary heat
cycle rate (CPH)
TH2210DV and
TH1210DV
9 Compressor
cycle rate (CPH)
13 Early Start (TH2110DV
and TH2210DV)
14 Temperature
display
15 Compressor
protection
20 Clock display
(TH2110DV and
TH2210DV)
25 Lower temperature
range (TH1100DV only)
40 Restore program
schedule to default
(TH2110DV and
TH2210DV)
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage,
avoid cycling the compressor quickly.
Settings & options (factory default in bold)
5
For gas or oil furnaces of less than 90% efficiency
1
For steam or gravity systems
3
For hot water systems & furnaces of over 90% efficiency
6
For electric furnaces
[Other cycle rate options: 2 or 4 CPH]
3
For hot water systems & furnaces of over 90%
efficiency
1
For steam or gravity systems
5
For gas or oil furnaces of less than 90% efficiency
6
For electric furnaces
[Other cycle rate options: 2 or 4 CPH]
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5, or 6 CPH]
1
On **See page 8
0
Off
0
Fahrenheit
1
Celsius
1
Five-minute compressor off time (See page 8)
0
No compressor off time
0
12-hour display
1
24-hour display
0
Standard range 40°F to 90°F (4.5°C to 32°C)
1
Lower range (for garage mode) 35°F to 90°F
(1.5°C to 32°C)
0
Off
1
On - program schedule default settings are listed in the
operating manual
7
PRO TH2000DV/TH1000DV Series