Nemo D4-Dc
Level 2
Password = 2001
2.1 Current input
CUrr SEC
Input:
dIrE A
direct connection 10A
60MV
shunt/60mV –
CUrr PrIM
Primary shunt: 1...9999A
ATTENTION!
Please make sure that the used wiring diagram perfectly meets the keyboard-made
connection type programming
Level 3
Password = 4321
3.1 Voltage input on site calibration
Level 4
Password = 5321
4.1 Current input on site calibration
Through the fed meter and the presence of the input signal, it is possible to carry out an
accurate calibration on site of the voltage and current nominal values.
Voltage and current controls are separate and independent.
Acting on the keyboard it is possible to adjust the input signal reading up to the nominal
value.
Example
Input nominal values: 24V and 80A
Values displayed by the meter: 24,1V and 79,9A
Act on the keyboard until you could read 24,0V and 80.0A, then press
amendment.
Level 5
Password = 7321
5.1 Restore of company settings
It restores all the parameters programmed in the factory, resetting all the ensuing loadings.
6
100MV
shunt/100mV –
150MV
shunt/150mV
to store the
Level 1
1.0
Password 1000
Pressing at the same time the
increases the loaded value
↵
moves the cursor
confirms
Load
Password 1000
and confirm
↵
confirms
+
keys
, you display page: