For example below:
Mode
Heating mode
Cooling mode
Water pump running logic and error code 'EE03/ON'.
There are two options for water pump running.
Option 1:Water pump starts or stops in relation to heat pump operation.
Water pump starts 60s before compressor, water pump start 30s and then detect the water flow switch. When the
heat pump meet the requirement of standby mode, water pump will stop 5mins after compressor stops. Water
flow switch won't be detected in 1H standby of heat pump. Even if the water flow switch is manually removed, the
EE03/ON error will not be reported. Water pump will restart to running for 5mins to check the water temp. when
the standby time is over 1 hours.
HP working mode
Heating mode
Cooling mode
In this case, it is unnecessary to deal with Error code 'EE03/ON' if 'EE03/ON' occurs in 1 hours standby period.
Option 2
No matter when the heat pump is on (running or standby), water pump will always be running.
Water pump will run for 1 minute after manually turn off.
Water out
Setting
temperature
temperature
36℃
29℃
23℃
30℃
Condition
(Tset:Setting water temp.
d1: Inlet water temp.)
d1>=Tset-0.5,
and last for 30 min
d1<=Tset+0.5,
And last for 30 min
Condition
Tout - Tset ≧7℃
Tset - Tout ≧7℃
Example:
Tset = 28℃,
d1>=27.5℃,
last for 30 minutes
d1<=28.5℃,
last for 30 minutes
26
Malfunction
EE04
Overheating protection for
water temperature (d2)
PP11
Too low protection for water
temperature (d2)
Water pump working logic
If heat pump enter standby mode for
1 hours, water Pump will start 5mins
d
to check whether
1>Tset-1
pump will go into standy again.
If d1<=Tset-1,heat pump will restart.
If heat pump enter standby mode for
1 hours, water Pump will start 5mins
d1<Tset+1,if
to check whether
so,heat pump will go into standy
again.
If d1>=Tset+1,heat pump will restart.
,if so,heat