Remarques
Code SAP
InspirAir
Home : Mémorisation Temporisée Réglages : $1234 (5s), $5678 (1s), $7890 (15s)
®
EasyVEC
®
: Mémorisation $1213, Reset C4 : $5452
InspirAir
Home : 0 = Auto, 1 = Hygro, 2 = Vitesse constante
®
EasyVEC
®
: Pression constante = 0, Debit constant = 1001, Courbe montante auto = 1002,
Courbe montante Hygro = 1003, Courbe montante T.Flow = 1004, Courbe montante parametrable
= 1005, 0_10V = 1006, C4 = 2512 .
0 = Vacances, 1 = Normal, 2 = Pointe Cuisine, 3 = Invités
0 = OFF, 1 = Auto, 2 = Optimisation Hiver, 3 = Optimisation Eté, 4 = Ouvert
0 = Vitesses séparées, 1 = Débits séparés, 2 = Pression Séparées, 3 = Courbe Montante
Si valeur > 0 alors boost desactivé, si valeur = 1 alors boost pendant 10 secondes, il faut renvoyer
toute les 10 secondes pour maintenir le mode boost, si > 1 alors on indique des minutes de boost
0 = Infini ; sinon : nb x 5 minutes (Max = 113 Jours)
0 = Infini ; sinon : nb x 5 minutes (Max = 113 Jours)
0 = Infini ; sinon : nb x 5 minutes (Max = 113 Jours)
En mois, (Max = 255)
0 = Infini ; sinon : nb x 5 minutes (Max = 113 Jours)
0 = Infini ; sinon : nb x 5 minutes (Max = 113 Jours)
% entre 0-200
0 = extraction, 1 = insufflation
InspirAir
Home : Présence iBus, BpCuisine Actif, Entrée 0-10V active, USB Actif, Radio Active
®
EasyVEC
: Entrée Filtre, entrée Boost
®
b0 = SW1 ... b7 = SW8
Liste des périphériques iBus : clavier Modulo, BCA Bus...
IHM installateur détectée : b0 = clavier Eco à membrane, b1 : cœur
IHM Utilisateur présents : Clavier UserCube à membrane, Clavier 2V « Bp Cuisine », Clavier 3V
« Modulo », Clavier 4V « RadioFilaire »
oui = 0, non = 1
heures
0 = Fermé, 1 = Ouvert, 2 = en fermeture, 3 = en ouverture, 4 = en court-circuit, 5 = en circuit
ouvert, 6 = sous-alimentation
0 ou > 0
Sonde de températeur extérieur x0.01°C
Sonde de températeur intérieure x0.01°C
0 = arrêt, 2512 = actif
InspirAir
Home : code problème (non bloquant)
®
Si envoi 0xFFFE alors la carte reboot
FR
Remarks
SAP code
InspirAir
Home: Settings time saving: $1234 (5s), $5678 (1s), $7890 (15s)
®
EasyVEC
®
: Saving = $1213 saving, C4 reset: $5452
InspirAir
Home: 0 = Auto, 1 = Hygro, 2 = constant speed
®
EasyVEC
®
: Constant pressure = 0, Constant airflow = 1001, Auto Adjusted pressure = 1002,
Hygro Adjusted pressure = 1003, T.Flow adjusted pressure, Customised Adjusted pressure = 1005,
0_10V = 1006, C4 = 2512 .
0 = Holidays, 1 = Standard, 2 = Kitchen High Speed, 3 = Guests
0 = OFF, 1 = Auto, 2 = Winter optimisation, 3 = Summer optimisation, 4 = Open
0 = Separated speeds, 1 = Separated airflows, 2 = Separated pressures, 3 = Adjusted pressure
If value > 0 the boost is off, if value = 1 the boost lenght is 10 secondes, if > 1 the boost lenght is
equal to the value set
0 = Infinite ; if not: nb x 5 minutes (Max = 113 days)
0 = Infinite ; if not: nb x 5 minutes (Max = 113 days)
0 = Infinite ; if not: nb x 5 minutes (Max = 113 days)
Months (Max = 255)
0 = Infinite ; if not: nb x 5 minutes (Max = 113 days)
0 = Infinite ; if not: nb x 5 minutes (Max = 113 days)
% between 0 and 200
0 = extract, 1 = supply
InspirAir
Home: iBus on, BpKitchen on, Entrée 0-10V entry on, USB on, Radio on
®
EasyVEC
: Filter entry, Boost entry
®
b0 = SW1 ... b7 = SW8
Auxiliary iBus list: Modulo keyboard, BCA Bus...
Installer HMI detected: b0 = Eco keyboard, b1 = heart
User HMI: UserCube keyboard, 2 speeds keyboard for kitchen, 3 speeds keyboard, 4 speeds
keyboard
Yes = 0, no = 1
Hours
0 = Close, 1 = Open, 2 = closing, 3 = opening, 4 = short-circuit, 5 = opened circuit,
6 = under supply
0 or > 0
Outdoor temperature sensor x0.01°C
Indoor temperature sensor x0.01°C
0 = off, 2512 = on
InspirAir
Home: non blocking error
®
If 0xFFFE: card reboot
3