Electrical installation

Power supply
Circuit breaker
RCCB
Pre-Installation
> Installing a permanent power supply line:
• Install separate circuit breaker and residual-current
circuit breaker (RCCB) upstream
• Connect all pole disconnector mains switches up-
stream located outside specified protection zones (0
- 2)
• Leave 3 000 mm of feed cable exposed
> Lay equipotential bonding cables:
• Leave 3 000 mm of cable exposed
10
connect whirltub
Malfunctions due to incorrect
NotIcE
installation
> Do not fasten the cables together with cable ties.
> Do not install the supply line parallel to the control
cables.
I
Connect the supply line to the mains supply socket.
II
Connect the potential equalisation cable to the
whirltub.
76xxx xx x xx00: 50 Hz, 220 - 240 V AC
76xxx xx x xx06: 60 Hz, 220 - 240 V AC
I
= 16 A
N
I
≤ 30 mA
ΔN
Safety areas in accordance with DIN VDE 0100-701
0
6 0
1
0
I
L
N
PE
II
6 0
0
2
* or the height of
the highest shower
head / water outlet
that is permanently
installed, depending
on which is higher
WH_M_Vero Air_FST/17.01.1
7