3 X 400V
Type
Capacité Alimentation él.
GOLD RX/PX/SD
04-05
TBLE-3-000-031-075-1 7,5 kW
TBLE-4-000-031-12-1
12 kW
TBLE-4-000-031-20-1
20 kW
TBLE-4-000-031-27-1
27 kW
TBLE-4-060-030-07-1 7,5 kW
TBLE-4-060-030-12-1
12 kW
TBLE-4-060-030-20-1 20 kW
TCLE-1-05 7,5 kW
7,5 kW
TCLE-1-05 12 kW
12 kW
GOLD RX/PX/SD 08
GOLD LP 05/
COMPACT LP 05
TBLE-4-000-040-06-1 6,0 kW 3X400V+N+terre 8,7 A
TBLE-4-000-040-12-1
12,0 kW 3X400V+N+terre 17,3 A
TBLE-4-000-040-20-1 20,0 kW 3X400V+N+terre 28,9 A
TBLE-4-000-040-27-1 27,0 kW 3X400V+N+terre 39,0 A
TBLE-4-000-040-36-1 36,0 kW 3X400V+N+terre 52,0 A
TBLE-4-000-040-47-1 47,0 kW 3X400V+N+terre 68,6 A
TBLE-4-080-040-06-1 6 kW
TBLE-4-080-040-12-1
12 kW
TBLE-4-080-040-20-1 20 kW
TBLE-4-080-040-27-1 27 kW
TBLE-4-080-040-36-1 36 kW
TCLE-1-08 6 kW
6,0 kW 3X400V+N+terre 8,7 A
TCLE-1-08 12 kW
12,0 kW 3X400V+N+terre 17,3 A
TCLE-1-08 20 kW
20,0 kW 3X400V+N+terre 28,9 A
TCLE-1-08 27 kW
27,0 kW 3X400V+N+terre 39,0 A
GOLD 12
TBLE-4-000-050-08-1 8,0 kW 3X400V+N+terre 11,6 A
TBLE-4-000-050-12-1
12,0 kW 3X400V+N+terre 17,3 A
TBLE-4-000-050-20-1 20,0 kW 3X400V+N+terre 28,9 A
TBLE-4-000-050-27-1
27,0 kW 3X400V+N+terre 39,0 A
TBLE-4-000-050-36-1 36,0 kW 3X400V+N+terre 52,0 A
TBLE-4-000-050-47-1 47,0 kW 3X400V+N+terre 68,6 A
TBLE-4-000-050-69-1 69,0 kW 3X400V+N+terre 99,6 A
TBLE-4-100-040-08-1-A 8 kW
TBLE-4-100-040-12-1-A 12 kW
TBLE-4-100-040-20-1-A 20 kW
TBLE-4-100-040-27-1-A 27 kW
TBLE-4-100-040-36-1-A 36 kW
TCLE-1-12 8 kW
8,0 kW 3X400V+N+terre 11,6 A
TCLE-1-12 12 kW
12,0 kW 3X400V+N+terre 17,3 A
TCLE-1-12 20 kW
20,0 kW 3X400V+N+terre 28,9 A
TCLE-1-12 27 kW
27,0 kW 3X400V+N+terre 39,0 A
TCLE-1-12 36 kW
36,0 kW 3X400V+N+terre 52,0 A
14-20
TBLE-4-100-040-08-1 8 kW
TBLE-4-100-040-12-1
12 kW
TBLE-4-100-040-20-1
20 kW
TBLE-4-100-040-36-1
36 kW
TBLE-4-100-040-47-1
47,5 kW 3x400V+N+terre 68,6A
TBLE-4-100-040-69-1 69 kW
TBLE-4-100-040-79-1
79 kW
TCLE-1-20 8 kW
8 kW
TCLE-1-20 12 kW
12 kW
TCLE-1-20 20 kW
20 kW
TCLE-1-20 36 kW
36 kW
TCLE-1-20 47,5 kW
47,5 kW 3x400V+N+terre 68,6A
* P-P = Pause - Impulsion
T = Thyristor
4
www.swegon.com
Intens.
Fusible
3X400V+N+terre 10,8 A
16 A
3X400V+N+terre 17,3 A
20 A
3X400V+N+terre 28,9 A
32 A
3X400V+N+terre 39,0 A
40 A
3X400V+N+terre 10,8 A
16 A
3X400V+N+terre 17,3 A
20 A
3X400V+N+terre 28,9 A
32 A
3X400V+N+terre 10,8 A
16 A
3X400V+N+terre 17,3 A
20 A
10 A
20 A
32 A
40 A
63 A
80 A
3X400V+N+terre 8,7 A
16 A
3X400V+N+terre 17,3 A
20 A
3X400V+N+terre 28,9 A
32 A
3X400V+N+terre 39,0 A
40 A
3X400V+N+terre 52,0 A
63 A
10 A
20 A
32 A
40 A
16 A
20 A
32 A
40 A
63 A
80 A
100 A
3X400V+N+terre 11,6 A
16 A
3X400V+N+terre 17,3 A
20 A
3X400V+N+terre 28,9 A
32 A
3X400V+N+terre 39,0 A
40 A
3X400V+N+terre 52,0 A
63 A
16 A
20 A
32 A
40 A
63 A
3x400V+N+terre 11,6A
16A
3x400V+N+terre 17,3A
20A
3x400V+N+terre 28,9A
32A
3x400V+N+terre 52,0A
63A
80A
3x400V+N+terre 99,6A
100A
3x400V+N+terre 114,0A
125A
3x400V+N+terre 11,6A
16A
3x400V+N+terre 17,3A
20A
3x400V+N+terre 28,9A
32A
3x400V+N+terre 52,0A
63A
80A
Signal/nombre d'étages*
P-P/T
P-P/T
14
P-P/T
P-P/T
P-P/T
P-P/T
P-P/T
P-P/T
P-P/T
P-P/T
P-P/T
P-P/T
P-P/T
0-10 V/T+1 étage
0-10 V/T+1 étage
P-P/T
P-P/T
P-P/T
P-P/T
0-10 V/T+1 étage
P-P/T
P-P/T
P-P/T
P-P/T
éléments chauffants disposés de
P-P/T
P-P/T
P-P/T
Brun
Blanc -brun ou brun clair = 24 V~(G0)
P-P/T
Orange
0-10 V/T+1 étage
0-10 V/T+1 étage
Blanc–bleu ou bleu clair = signal de commande U
0-10 V/T+2 étages
P-P/T
Bleu
P-P/T
Blanc-orange ou blanc
P-P/T
Vert
P-P/T
Blanc-vert ou vert clair
0-10 V/T+1 étage
P-P/T
P-P/T
P-P/T
P-P/T
0-10 V/T+1 étage
P-P/T
P-P/T
P-P/T
0-10 V/T+1 étage
0-10 V/T+1 étage
0-10 V/T+2 étages
0-10 V/T+2 étages
P-P/T
P-P/T
P-P/T
0-10 V/T+1 étage
0-10 V/T+1 étage
Sous réserve de modifications sans avis préalable.
FR.TBLE.170912
Régulateur, batterie de
chauffage électrique
15
Câble de commande (com-
plètement câblé)
Pour batteries de chauffage à
raccords circulaires
7 6
câble de commande (complète-
ment câblé)
Pour batteries de chauffage à
manière rectangulaire.
= 24 V~(G)
= Signal de commande Y
(0-10 V)
(ne pas utiliser!)
= Surchauffe
= Surchauffe (Terre)
= Batterie de chauffage,
type (résistance)
= référence (Terre)